6.11.6 “Standard / American” selection, Software Version
CONFIGURATION
Drive type
[465]
Drive size [A]
[201]
2B + E
[464]
Size selection
[331]
Software version
Parameter description
No.
Value
Standard
Configuration
min
max
Factory
American
Factory
Standard
Drive size [A]
465
0
S
S
S
-
2B + E
ON (Off) (0)
OFF (On) (1)
201
0
1
0
0
-
Size selection
Standard (0)
American (1)
464
0
1
1
0
-
Software version
331
-
Drive type
TPD32-EV-...-2B
TPD32-EV-...-4B
300
10
11
S
S
-
Drive size
Display of the converter armature current in ampere (it is codified by the SW15 Switch
placed on the R-TPD32-EV regulation card). The stated value depends on the setting
of the
Size selection
parameter.
2B + E
Selection of the 2B + external excitation configuration. Only for 2B converters. The
function allows the drive to work with an external 4 quadrant field controller. When
the parameter is On the Ramp / Speed / T current references and Speed measurement
have the same behaviour of the 4B drive.
Size selection
With the “Standard” selection the converter produces rated current in a continuative
way in the preset ambient conditions without overload (for overload see 6.14.5). With
“America” selection the rated current is defined considering an overload of 1.5 times for
60 seconds. This causes a reduction of the converter rated current (continuative current)
for the same type of drive. See section 4.4, R-TPD32-EV Regulation card.
Standard
The converter produces rated current in a continuative way.
It is stated as
Drive size
. No overload functions are set.
American
The rated current (produced continuously) will be reduced to
the value stated in the mentioned table and indicated in
Full
load current
and
Drive size
parameters.
Automatically, the overload function (FUNCTION\Overload
control), is set to the following:
Enable overload
= ON
Overload mode
= I2t motor
Overload time
= 60s
Full load current
= American
Pause time
= 540s
T current lim
= 150%
Overload current
= 150%
T current lim+
= 150%
Base current
= 100%
T current lim -
= 150%
If the size “American”is selected, the parameter
Overcurrent thr
[584] will be set at 160%
n
ote
!
If the converter is reconfigured as “Standard”, these parameters and the continuous current
limit take the values corresponding to the previous configuration (overload disabled) and the
parameter
Overcurrent thr [584]
returns to 110%.
Software version
Display of the software version number active in the converter.
Drive type
Display of the drive type: 2B or 4B.
Summary of Contents for TPD32-EV-...-2B
Page 1: ... Instruction manual Industrial Application DC drives TPD32 EV ...
Page 372: ... TPD32 EV 372 9 BLOCK DIAGRAM 9 1 CONTROL BLOCK DIAGRAMS ...
Page 373: ... Instruction manual 373 ...
Page 374: ... TPD32 EV 374 ...
Page 375: ... Instruction manual 375 ...
Page 376: ... TPD32 EV 376 ...
Page 377: ... Instruction manual 377 ...
Page 378: ... TPD32 EV 378 ...
Page 379: ... Instruction manual 379 ...
Page 380: ... TPD32 EV 380 ...
Page 381: ... Instruction manual 381 ...
Page 382: ... TPD32 EV 382 ...
Page 383: ... Instruction manual 383 ...
Page 384: ... TPD32 EV 384 ...
Page 385: ... Instruction manual 385 ...
Page 386: ... TPD32 EV 386 ...
Page 387: ... Instruction manual 387 ...
Page 388: ... TPD32 EV 388 ...
Page 389: ... Instruction manual 389 ...
Page 390: ... TPD32 EV 390 ...
Page 391: ... Instruction manual 391 ...
Page 392: ... TPD32 EV 392 ...
Page 393: ... Instruction manual 393 ...
Page 394: ... TPD32 EV 394 ...
Page 395: ... Instruction manual 395 ...
Page 396: ... TPD32 EV 396 ...
Page 397: ... Instruction manual 397 ...
Page 398: ... TPD32 EV 398 ...
Page 399: ... Instruction manual 399 ...
Page 400: ... TPD32 EV 400 ...
Page 401: ... Instruction manual 401 ...
Page 402: ... TPD32 EV 402 ...
Page 501: ... Instruction manual 501 APPENDIX 3 ACCESSORIES A3 1 EAM Adapter Kit EAM1579 EAM1580 ...
Page 503: ......