4 - Wiring Procedure
4.1 Power Section
Terminals
Function
U1/L1, V1/L2, W1/L3
AC mains voltage (230V -15% ... 480V +10%)
BR1
Braking unit resistor command (braking resistor must be connected between BR1
and C)
C, D
Intermediate circuit connection (770 Vdc, 1.65 x I
2N
)
U2/T1, V2/T2, W2/T3
Motor connection (AC line volt 3Ph, 1.36 I
2N
)
PE2
Motor ground connection
EM
(**)
Emergency module signal required to interface the drive with the EMS device (Emer-
gency Module Supplier ), max 0,22A
FEXT
(**)
Logic fan control signal repeated on an external fan (*)
250V, 1A.
PE1
Ground connection
(*)
Fans will be always start when the drive is enabled. Fans will stop when the drive is disabled after a period of 300
sec. and heatsink temperature is below 60°C.
(**)
EM and FEXT terminals are available on sizes 3110 ... 5550.
Note!
Use 60°C / 75°C copper conductor only.
The grounding conductor of the motor cable may conduct up to twice the value of the rated current if essere
there is a ground fault at the output of the drive.
External fuses of the power section
The inverter must be fused on the AC Input side.
Use superfast semiconductor fuses only.
Connections with three-phase inductance on AC input will improve the DC link capacitors life time.
230 … 400 Vac, 50Hz
230 … 400 Vac, 50Hz
2040
GRD2/20 or Z14GR20
A70P20
FWP20
GRD2/16 or Z14GR16
A70P20
FWP20
2055
GRD2/25 or Z14GR25
A70P25
FWP25
GRD2/20 or Z14GR20
A70P20
FWP20
2075
GRD3/35 or Z22GR40
A70P35
FWP35
GRD2/25 or Z14GR25
A70P25
FWP25
3110
GRD3/50 or Z22GR40
A70P40
FWP40
GRD3/50 or Z22GR40
A70P35
FWP35
3150
GRD3/50 or Z22GR50
A70P40
FWP40
GRD3/50 or Z22GR50
A70P40
FWP40
4185
4221
4301
S00C+üf1/80/80A/660V or Z22gR80
A70P80
FWP80
4371
S00C+üf1/80/100A/660V or M00üf01/100A/660V
A70P100 FWP100
5450
5550
6750
7900
71100
71320
81600
82000
S2üf1/110/500A/660V or M2üf1/500A/660V
A70P500 FWP500
fusibili-g
S2üf1/110/400A/660V or M2üf1/400A/660V
A70P400 FWP400
S1üf1/110/250A/660V or M1üf1/250A/660V
A70P300 FWP300
For these types an external reactor is mandatory if the AC
input impedence is equal or less than 1%
Type
Fuses
Fuses
460 Vac, 60Hz
460 Vac, 60Hz
Connections without three-phase reactor on AC input
Connections with three-phase reactor on AC input
GRD3/50 or Z22GR50
A70P50
FWP50
S00C+üf1/80/160A/660V or M00üf01/160A/660V
A70P175 FWP175
Fuse manufacturers:
Type GRD... , Z14... 14 x 51 mm, S... , M... ,Z22... 22 x 58 mm Jean Müller, Eltville
A70...
Ferraz
FWP...
Bussmann
Caution
Summary of Contents for SIEIDrive LIFT AGy -L
Page 1: ... Instruction manual SIEIDrive LIFT Lift vector AC Drives AGy L ...
Page 46: ...Italiano 46 AGy L ...
Page 90: ...English 90 AGy L ...
Page 134: ...Français 134 AGy L ...
Page 178: ...Deutsch 178 AGy L ...
Page 222: ...Español 222 AGy L ...
Page 240: ...NOTE ...
Page 241: ......