81901A “MSW_GPC-40/600A”_03-2021_ENG_page 25
3.8.8.
Power factor
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1740
716
16 bit
CoS.F
M
MainMenu
→
M
→
Status
→
CoS.F_1
R
Float
(####.#)
2764
E1
MainMenu
→
E1
→
Status
→
CoS.F_2
4812
E2
MainMenu
→
E2
→
Status
→
CoS.F_3
The parameter shows the power factor of the device M or E1 or E2.
3.8.9.
RMS load current
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1777
753
16 bit
01.02.06
Ld.A
M
MainMenu
→
M
→
Status
→
Ld.A_1
R
Float
(####.#)
A
2801
01.03.06
E1
MainMenu
→
E1
→
Status
→
Ld.A_2
4849
01.04.06
E2
MainMenu
→
E2
→
Status
→
Ld.A_3
The parameter shows the RMS load current input of device M or E1 or E2.
3.8.10.
RMS current in three-phase load
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1778
754
16 bit
01.01.02
Ld.A.t
Global MainMenu
→
Global
→
Status
→
Ld.A.t
R
Float
(####.#)
A
The parameter shows the RMS current input of the three-phase load.
3.8.11.
Ammeter input digital filter
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1243
219
16 bit
04.08.04
Ft.tA
M
MainMenu
→
M
→
Inputs
→
CT input
→
Ft.tA_1
R/W
■
Float
(####.#)
sec.
0.1
2267
04.11.04
E1
MainMenu
→
E1
→
Inputs
→
CT input
→
Ft.tA_2
4315
04:14:04
E2
MainMenu
→
E2
→
Inputs
→
CT input
→
Ft.tA_3
The parameter sets the time constant value of the digital filter applied to the CT ammeter input of device M or E1 or E2. The filter calcu-
lates the average of the values read in the specified time interval. With 0.0 no filter is applied.
min...max
:
0.0
...
20.0