81901A “MSW_GPC-40/600A”_03-2021_ENG_page 121
3.33. Heterogeneous power control
The Heterogenous power control function is like a program-
mable circuit breaker. It allows the user to set a maximum
power to be used by the device in its entirety. If the maxi-
mum is reached then specific parts of the load are switched
off (disconnected) according to a predefined priority.
GPC-M always has priority and is switched off last. If power
control is enabled for several modules, the disconnection
sequence starts with the module with the highest number
(GPC-E2 before GPC-E1 and GPC-M, GPC-E1 before
GPC-M).
3.33.1.
Enabling heterogeneous power control
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1706
682
16 bit
09.08.01
hd.4
Global
MainMenu
→
Global
→
Powers
→
hd.4
R/W
■
Unsigned
Short
0
The parameter enables heterogeneous power control of GPC-M, GPC-E1 and GPC-E2. Setting
hd.4
= 0 disables heterogeneous power
control for all modules.
Options
:
Index
GPC-M
enabled
GPC-E1
enabled
GPC-E2
enabled
0
1
■
2
■
3
■
■
4
■
5
■
■
6
■
■
7
■
■
■
3.33.2.
Maximum current for heterogeneous power control
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1707
683
16 bit
09.08.02
I.HEt
Global MainMenu
→
Global
→
Powers
→
I.HEt
R/W
■
Float
(####.#)
A
0.0
The parameter sets the maximum current for heterogeneous power control.
min...max:
0.0
...
3275.0