81901A “MSW_GPC-40/600A”_03-2021_ENG_page 103
3.23.3.
Enabling manual power correction and storage
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1042
18
16 bit
07.01.01
SP.r
Global MainMenu
→
Global
→
Controls
→
SP.r
R/W
■
Unsigned
Short
0
The parameter enables manual power correction and storage.
Options:
0
= No function
8
= Manual power correction based on mains voltage
32
= Disabling of local manual power storage (the last stored value is retrieved when switching off)
3.24. Start modes
3.24.1.
Start mode at Power-On
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1723
699
16 bit
07.02.09
P.Ont
M
MainMenu
→
M
→
Controls
→
P.Ont_1
R/W
■
Unsigned
Short
0
2747
07.03.09
E1
MainMenu
→
E1
→
Controls
→
P.Ont_2
4795
01.04.09
E2
MainMenu
→
E2
→
Controls
→
P.Ont_3
This parameter sets the mode in which the Advanced Power Controller starts up when power is supplied.
The mode is identified by an index.
Options
:
Index
Start modes
0
Operation of the controller resumes with the same
modalities as the last state prior to shutdown. Digital
input states always take priority over other states.
1
Software shutdown.
2
Software startup.