23
80999D_MHW_GFW 400-600A_07-2020
_ENG
3.4
D
escriPtion
of
DiP
-
switches
Figure 22
Connector J5
12
34
56
7
ON
Table 17
dip-switches
Decription
1
Connection type: (see table 23)
2
Connection type: (see table 23)
3
Connection type: (see table 23)
4
Connection type: (see table 23)
5
OFF = resistive load
ON = inductive load (transformer primary control)
6
ON = reset factory configuration
7
ON = Geflex simulation function
Table 18
OFF: resistive load
ON :inductive load
(transformer primary control)
R e q u e s t
modules
GFW master
GFW Expansion 1
GFW Expansion 2
Dip 1
Dip 2
Dip 3
Dip 4
Dip 5
Connection type
OFF
OFF
OFF
OFF
OFF/ON
Three Single-phase load
x
(*) (*)
OFF
ON
OFF
OFF
OFF/ON
Three Independent single-phase load in open delta
x
x
x
ON
ON
OFF
OFF
OFF/ON 3-phase load open delta/star load with neutral
x
x
x
ON
ON
ON
OFF
OFF/ON
3-phase load closed delta
x
x
x
ON
OFF
OFF
ON
OFF/ON
3-phase star load without neutral
x
x
x
ON
OFF
OFF
OFF
OFF/ON 3-phase star load without neutral with 2-phase command
x
x
ON
OFF
ON
OFF
OFF/ON 3-phase load closed delta with 2-phase command
x
x
(*) Each expansion lets you add a single-phase load (up to a maximum of 3 total loads).
IMPORTANT!
AFTER SETTING THE REQUIRED DIP-SWITCH CONFIGURATION, RUN THE FOLLOWING PARAMETER
INITIALIZATION PROCEDURE ONCE:
-
CHECK THE CORRECT SETTING OF DIPS 1-2-3-4-5
-
SET DIP 6 TO “ON” (FACTORY CONFIGURATION)
-
POWER THE DEVICE WITH 24 VDC
-
WAIT FOR CORRECT AND REGULAR FLASHING OF THE GREEN RUN LED
-
SET DIP 6 TO “OFF”
-
THE DEVICE IS CORRECTLY CONFIGURED