99
10
45
45
48
70
70
63
48
105
10
108
96
48
44,5
92
70
115
Triac output
(option, only for 96 format)
20...240Vac ±10%, 3A max
Snubberless, inductive and resistive load (I
2
t = 128A
2
s)
Transmitter / Sensor Power Supply
1.2 Vdc for potentiometer > 100
Ω
5 Vdc, 10 Vdc max. 120mA, (for strain-gauge)
15 Vdc, 24 Vdc max. 50mA, (for transmitter)
Fault settings
Alarm states can be configured in probe fault
condition
Analog retransmission (option)
4 to 20mA, max. 150
Ω
load
Logic input
Ri = 5,6K
Ω
(24V, 4mA), 1500V isolation
Logic input functions
configurable for alarm memory reset, hold, flash,
zero, selection of max., min. peak value, peak-peak
Power supply (switching)
40B 48 (std) 100...240Vac ±10%, 8VA
(optional) 20...27Vac/dc ±10%, 8VA
40B 96 (std) 100...240Vac/dc ±10%, 10,5VA
(optional) 11...27Vac/dc ±10%, 8VA
For correct and safe
installation, follow the
instructions and observe
the warnings contained
in this manual.
1 • INSTALLATION
• Dimensions and cut-out: Panel mounting
Panel mounting:
Fix the device with the bracket provided before making any electrical connections.
To mount two or more devices side by side, use the cut-out dimensions shown above.
CE MARKING: EMC (electromagnetic compatibility) conformity to EEC Directive
89/336/CEE with reference to the generic Standard EN50082-2 (immunity in industrial
environments) and EN50081-1 (emission in residential environments). BT (low voltage)
conformity to Directive 73/23/CEE as modified by Directive 93/68.
MAINTENANCE: Repairs must be done out only by trained and specialized personnel.
Cut power to the device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene, etc.).
Use of these solvents can reduce the mechanical reliability of the device. Use a cloth
dampened in ethyl alcohol or water to clean the external plastic case.
SERVICE: GEFRAN has a service department. The warranty excludes defects caused
by any use not conforming to these instructions.
2 • TECHNICAL SPECIFICATIONS
FUNCTION
CABLE
LENGTH USED
Input
1 mm
2
3 m
Power supply cable
1 mm
2
1 m
Relay output cables
1 mm
2
3,5 m
EMC conformity has been tested with the following connections
!
40B 48 / 40B 96
POSITION, FORCE and PRESSURE INDICATOR-INTERCEPTOR
with INPUT for STRAIN-GAUGE and POTENTIOMETER
SOFTWARE VERSION 1.0x / 2.0x
code 81651C / edition 09 - 03/08
USER’S MANUAL
Faceplate protection
IP65
Working / Storage temperatures
0 to 50°C / -20 to 70°C
Relative humidity
20 to 85%, non-condensing
Installation
Panel mounting, extractable from front
Weight
160g (mod. 48); 320g (mod. 96) for the complete version
Relay contact
NO (NC) 5A, 250V
Logic output
11Vdc, Rout = 220
Ω
(6V/20mA)
Fuse (inside device, not
operator serviceable)
100 to 240Vac/dc - type T - 500mA - 250V
11 to 27Vac/dc - type T - 1.25A - 250V
Resolution
function of settable sample time
>13-bit, s.t. 120 msec. with probe power supply control
>12-bit, s.t. 30 msec.
(60msec with probe power supply control)
>11-bit, s.t. 15 msec.
(30msec with probe power supply control)
Linear scale ranges
-1999 to 9999 (with 4 digit display)
-999 to 999 (with 3 digit display - only for model 96)
Configurable decimal point position, possible 32
segment linearization
Alarms (set points)
Maximum of three configurable alarms:
absolute, deviation, symmetrical deviation.
Adjustable hysteresis
Alarm masking
ability to:
- exclude on power-up
- latch reset from key and/or external contact
- insert delay filter (DON, DBI, DOF, DPO)
- set minimum intervention time
Display
3, 4 digit red LED’s
mod. 48 digit height 10mm (4 digits)
mod. 96 digit height 20mm (3 digits),
digit height 14mm (4 digits)
Keys
3 mechanical keys (Raise, Lower, F)
Accuracy
0.2% f.s. at 25°C ambient temperature, ts=120msec
Main input
Differential input:
- from strain-gauge 350
Ω
(for pressure, force, etc.),
sensitivity 5mV/V with strain-gauge max power
15V, (7.5mV/V with max power 10V - 15mV/V with
max power 5V), positive or symmetrical
polarization, calibration with automatic calibration
of sensitivity, interrupted probe power signal
- from potentiometer with 1.2V
≥
100
Ω
power
supply
1
81651C_MHW_40B48-96_0308_ENG