Chapter 6 Parameter • 236
ARTDrive V2 series - Instruction Manual
FLUX / Magnetizing configuration
The function is active only in a Sensorless and Field oriented mode and is useful for
undesired motor shaft rotation.
It allows to lock the flux position, Lock flux, and to set a Ramp time of the magnetizing
current
H01.00 - Magn ramp time
.
In the configurations it is possible to start the Lock flux function. Via the
H01.01 - Lock
flux pos
parameter, it is possible to lock the flux position when the following selected
condition is satisfied:
· Off
non-active function
· At magnetization
during magnetization
· At Spd=0
with Speed 0 delay signal
· At magn & Spd=0
during magnetization and with a Speed 0 delay signal
· At magn and Ref=0
during magnetization and Ref 0
· At Ref=0
with Reference 0
N
OTE
!
In order to have a better performances of Autocapture (Catch on Fly) function, it is
recommended to set
H01.01 - Lock flux pos
= At Ref = 0.
Furthermore, in
H01.00 - Magn ramp time
it is possible to set the magnetizing current
ramp time in seconds, which can be used:
•
To slow down the temporary magnetizing period and avoid a rotation of the motor
shaft due to the stator-rotor alignment
•
To speed up the magnetizing phase
H01 FLUX / Magn cfg
H01.00 Magn ramp time
[sec] RWS
DrvSize
0.01/5.00
PP
F-S-B
Easy 1810
Magnetizing current ramp time.
H01.01 Lock flux pos
N/A
RWSZ (*)
0/5
DP
F-S-B
Easy 1815
It is allows to lock the flux position when the following selected condition is satisfied (see
descriptions above):
[0] Off
[1] At Magnetiz
[2] At Spd=0
[3] At Magn&Spd=0
[4] At Magn&Ref=0
[5] At Ref=0
N
OTE
!
For Autocapture function in Sensorless reg. mode, enabling of Autocapture (Catch
on Fly) function if required and
H01.01 - Lock flux pos
parameter must be set at
“Ref = 0”
Summary of Contents for ARTDrive Vector V2 400Vac Series
Page 1: ...Instruction Manual ARTDrive ARTDrive Vector AC Drives V2 series 400Vac Class 575Vac Class...
Page 14: ...0 14 Chapter 0 Safety Precautions ARTDrive V2 series Instruction manual...
Page 40: ...40 Chapter 3 Installation Guidelines ARTDrive V2 series Instruction Manual...
Page 92: ...92 Chapter 5 Quick Start Up Guide ARTDrive V2 series Instruction Manual...
Page 358: ...358 Chapter 8 Appendix ARTDrive V2 series Instruction Manual...
Page 376: ...Chapter 9 Pick Lists 376 ARTDrive V2 series Instruction manual...