6.6.7
Mounting to Valve N_/E or W_/E or STERICOM Valve
Requirement:
•
Pay attention not to kink the air hoses when mounting the control top.
Notice
The permanent magnet on the switch bar is fragile.
Damage to the permanent magnet.
► Protect the permanent magnet against impact stress.
Notice
Magnetic fields resulting from the permanent magnet on the
switch bar.
Magnetic fields can delete data carriers and affect or destroy electronic or
mechanical components.
► Protect the components against the magnetic fields from the switch bar.
Carry out the following steps:
1.
Complete the T.VIS mounting base (198) with O-rings (29, 101) and a plain
bearing (202).
Fig.37
Fig.38
2.
Screw the adapter T.VIS E/SHO (139) into the actuator with open-end wrench
on wrench surface (139.1) and tighten.
3.
Screw the mounting base (198) into the actuator (A.3) via the adapter T.VIS
E/SHO (139) and tighten using a face spanner.
4.
Screw the switch bar T.VIS (1) into the adapters T.VIS E / SHO (139) and
tighten with open-end wrench at (1.2), torque 2 Nm.
5.
Place the control top over the T.VIS switch bar (1) and on the actuator.
6.
Tighten the clamp connection (15) with screws (39) at a torque of 1 Nm.
7.
Align the pneumatic and electrical connections in accordance with the valve
block configuration.
Assembly and installation
Mounting the Control Top to Different Valves
430BAL010697EN_2
68
15.04.2020