2
stop. If the desired setting differs from the factory setting
it can be adjusted as follows: (See diagram)
a. Remove sealing cap (3).
b. Insert enclosed 2mm allen key (2) into adjustment
screw (1).
c. Turn allen key clockwise (+) to increase, or
counterclockwise (-) to decrease pressure setting.
Do not turn adjustment screw more than 3 turns
clockwise (+3).
The dead band control loop with dead band ‘P1’
switches the single stage compressors on or off,
1 turn causes a pressure change of approximately 2.6
bar.
Connections to the controller as below, (See wiring
diagrams for further info.)
Adjustment of FSC - Control Point
(Units with EC Fans)
Units fitted with EC fans, listed with electrical option ‘E’
in their part number use the Alco EC552 controller to
monitor and control the head pressure.
The control set point can be adjusted by changing the
parameter P0 in the condensing section of the
controller, ensure the Fan LED “
Set-up / Parameter Modification using the Keypad
” is lit in the display
to avoid accidental adjustment of the compressor set
point. See section F for more information.
The controller is factory set to maintain a suction
pressure of 3.5 BarG on HT units, and 0.8 BarG on LT
units, this can be modified during commissioning as
described below.
d) Compressor Manual Motor Starter/Overload –
Each compressor is supplied via a MMS/Overload,
which should be set to the maximum running current as
shown on the compressor nameplate during
commissioning. In the event of too high a current or
phase loss occurring the MMS will trip out and stop the
compressor, requiring a manual reset.
WARNING: Do not set the controller outside of the
application limits as shown in section 4.
The parameters can be accessed via the 4-button
keypad. The configuration parameters are protected by
a numerical password. The default password is “12”.
Please refer to the parameters table on page 5
To select the parameter configuration:
e) Compressor Contactor – Each compressor supply
is switched via a contactor. The contactor is controlled
via the Compressor Step Controller, and integrates the
compressor safety chain of the HP/LP’s and
MMS/Overloads.
1. Press the
button for more than 5 seconds
2. A flashing 0 is displayed
3. Press
or
until 12 is displayed; (password)
4. Press
f) Optional Compressor Step Controller – Units with
EC fans and electrical option ‘E’. The starting and
stopping of the compressors is controlled by an
electronic controller (EC2). The controller monitors the
suction pressure via a transducer and brings
compressors in or out to maintain the suction pressure
about the desired setting. Discharge pressure is also
monitored but not used for control purposes unless EC
fans are fitted.
to confirm password
5. The first modifiable parameter code is displayed (/1).
6. Press
or
to show the code of the parameter
that has to be changed;
7. Press
to display the selected parameter value;
8. Press
or
to increase or decrease the value;
9. Press
to temporarily confirm the new value and
display its code.
To adjust the Suction Target Setpoint modify the ‘P0’
parameter in the compressor section of the controller,
ensure the Compressors LED “
10. Repeat the procedure from point 6 to modify any
other parameters.
” is lit in the display
to avoid accidental adjustment of the condenser set
point. See below for more information.
11. Press
to confirm the new values and exit the
parameters modification procedure.
IMPORTANT : All EC2 controllers are fitted with a
dedicated 24V transformer that is not earthed. The EC2
controllers must not be earthed. Do not fit any other
electrical equipment to the EC2’s transformer.
Temporary Display Of Data:
It is possible to temporarily display the values of the
different sensors. This is a useful feature when initially
setting-up the system without the aid of the WebPages.
Suction Pressure Control EC2-552
2 control loops with the same suction pressure setpoint
‘P0’ modulate the compressors on and off.
Press the
sequentially. The value displayed on the
screen corresponds to the number corresponding to the
Summary of Contents for Searle NCE Series
Page 10: ...11a SCQ All Units 1MX A SCQ 611 06 XXX W Single Phase with AC Fans 10 ...
Page 11: ...11b SCQ All Units 3MX A SCQ 613 06 XXX W Three Phase with AC Fans 11 ...
Page 14: ...11e NSQ NSE15 1MX A 44 611 16 XXX W ZB15 Single Phase with AC Fans 14 ...
Page 16: ...11g NSQ NSE19 to 26 1MX A B or C 44 611 06 XXX W ZB19 to ZB26 Single Phase AC Fans 16 ...
Page 18: ...11i NSQ NSE15 to 45 3MX A B C 44 613 06 XXX W ZB15 to ZB45 Three Phase AC Fans 18 ...
Page 20: ...11k NDQ 30 to 45 3MX S C 44 613 XDX W ZBD30 to ZBD45 Three Phase AC Fans 20 ...
Page 21: ...11l NCQ NCE 56 to 110 3MX S D E 2 3 44 633 16 XXX W ZB56 to ZB11 Three Phase AC Fans 21 ...
Page 22: ...11m NSQ NSE 15 to 30 1MX S A B C 2 3 44 611 ST2 Layout Diagram 22 ...
Page 23: ...11n NSQ NSE 09 to 18 3LX S 15 to 45 3MX S A B C 2 3 44 613 ST2 Layout Diagram 23 ...
Page 24: ...11o NCQ NCE 24 to 48 3LX S 56 to 110 3MX S D E 2 3 44 633 3 ST2 Layout Diagram 24 ...
Page 25: ...12 DIMENSIONS Case A B C 25 ...