3.13.4
No Pump
This option is selected if the compressor is not equipped with an external oil pump. In this situation, the oil pres-
sure differential is maintained by the compressor.
3.14
IntelliSOC
An electronic modulating valve is provided to control the oil cooling. The position of the valve is based on the
discharge or oil temperature. The desired temperature is an operator-adjustable parameter. The modulating
valve is held closed for two seconds after the shutoff solenoid is energized to allow pressure to build against the
control valve.
The modulating valve will calibrate itself every time the compressor is successfully stopped from the running
state. While calibrating, the valve will be set to 4mA and fully close to its 0% position. It will remain in this state
for a period of time as defined in the
Calibrate Time Before Bleed
parameter. Following the delay, the valve will
remain at its minimum position until the compressor is started. At its minimum position, the valve is permitted to
open slightly to prevent liquid from becoming trapped between the valve and the shutoff solenoid.
Control
IntelliSOC
Instruction Manual | GEA Omni™
Control panel
206
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Summary of Contents for Omni
Page 1: ...Control panel GEA Omni Instruction Manual E_806550_2 ...
Page 238: ......