Value
Description
Volume Slide Position
This value displays the current reading of the volume slide position sensor. The
value is measured in percent. This point may monitor either a 4-20 mA signal or a
potentiometer input.
Primary Slide Position or
Swept Volume in %
This value displays the current reading of the primary slide position or swept vol-
ume. It is used for applications were an analog output module is provided to
retransmit the current reading of the primary slide position sensor. The value is
measured in percent. The default location for the module is dependent on where
the panel was configured.
Motor Current
This value displays the current reading of the compressor motor current sensor.
The value is measured in Amps. It will not appear on a slice if Motor Starter Com-
munication is enabled in the configuration. This point may monitor either a 4-20
mA signal or a current transformer input.
3.7.2
Standard Calculated Values
Hint!
These entries in the operating data table are not tied to a default position in the I/O system.
They are calculated by the system.
Value
Description
Loop time
This value represents the amount of time the system requires to execute all cus-
tom logic once and update all inputs and outputs. The value is measured in sec-
onds.
Oil Filter Differential
This value displays the calculated differential in the oil filter. The calculation used
is dependent on the compressor’s configuration. The value is measured in the cur-
rent pressure units of the panel.
Oil Differential
This value displays the calculated oil differential in the compressor. The calculation
used is dependent on the compressor’s configuration. The value is measured in
the current pressure units of the panel.
Motor Current
This value displays the value of the motor current as read through the motor
starter communication. It will not be visible if Motor Starter communication has not
been enabled in the configuration. The value is measured in Amps.
Cycle On Timer
This value displays the remaining time before the compressor will restart automati-
cally. It will only be visible if Automatic Start/Stop is enabled in the configuration.
The value is measured in seconds.
Control
Compressor Operating Data
Instruction Manual | GEA Omni™
Control panel
178
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016