3.4.2
Variable Speed Fan/Variable Speed Pump
Hint!
These parameters will only appear if the device in question is variable speed.
Parameter
Units
Minimum
Maximum
Default
Proportional Term
Unitless
0.0
500.0
250.0
Integral Term
s/R
1.0 s/R
250.0 s/R
40.0 s/R
Mode
Selection – See Description
Manual Mode Position
Percent
0.0 %
100.0 %
0.0 %
100.0 %
1.
Proportional Term
This parameter is used to set the proportional gain for PI control of the device. This value is multiplied by the
total error between the actual and desired values. The value is unitless.
2.
Integral Term
This parameter is used to set the rate at which the PI controller will change its integral gain based on the
calculated error over time. The value is measured in samples per Repeat (s/R).
3.
Mode
This parameter is used to select whether the PI controller will vary the output automatically or if it will be
controlled manually through the
Manual Mode Position
parameter. The options are
Auto
and
Manual
.
4.
Manual Mode Position
This parameter is used to set the desired output of the PI controller while it is operating in manual mode. The
value is measured in percent.
Hint!
This parameter will only appear if the Mode parameter is set to Manual.
3.4.3
Water cooled condenser
Parameter
Units
Minimum
Maximum
Default
Start Condition
None
0 = None
1 = Compressor controlled
Feedback Condenser Unit Warning
Delay
Seconds
0 s
300 s
0 s
Control
Condenser Device Control Parameters
Instruction Manual | GEA Omni™
Control panel
164
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Summary of Contents for Omni
Page 1: ...Control panel GEA Omni Instruction Manual E_806550_2 ...
Page 238: ......