6.
Water Pump Lockout Next Device Delay
This parameter is used to select the period of time that the condenser will wait after disabling a device during
water pump lockout before disabling each subsequent device. The value is measured in minutes.
7.
Water Pump Lockout Previous Device Delay
This parameter is used to select the period of time that the condenser will wait after enabling a device while
exiting water pump lockout before enabling each subsequent device. The value is measured in minutes.
3.4
Condenser Device Control Parameters
Control parameters are displayed on the main Condenser screen detailed in Section 2.6.2, Page 39. Below is a
list of all control parameters and a brief description of their function.
3.4.1
Control
Parameter
Units
Minimum
Maximum
Default
Runtime
Hours
0 h
1000000000 h
0 h
Number of Starts
Unitless
0
1000000000
0
Interlock Delay
Seconds
3 s
20 s
5 s
High to Low Speed Delay/Two
Speed Fan
Seconds
2 s
240 s
120 s
1.
Runtime
This parameter is used to display the total time the condenser device has been running. It may be manually
changed or reset to zero using the keypad. The value is measured in hours.
2.
Number of Starts
This parameter is used to display the total number of times the condenser device has been started. It may
be manually changed or reset to zero using the keypad. The value is unitless.
3.
Interlock Delay
This parameter is used to select the period of time for which an interlock fault must persist before a warning
condition will be annunciated. The value is measured in seconds.
4.
High to Low Speed Delay/Two Speed Fan
This parameter is used to select the period of time that a two speed fan device will wait before switching
from high to low speed. The value is measured in seconds.
Hint!
This parameter will only appear on two stage fan devices.
Instruction Manual | GEA Omni™
Control panel
Control
Condenser Device Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
163
Summary of Contents for Omni
Page 1: ...Control panel GEA Omni Instruction Manual E_806550_2 ...
Page 238: ......