8.
Limitation Suction Pressure Force Unload Offset
This parameter is used to set an offset value added to the
Low Suction Pressure Shutdown
parameter. If the
suction pressure falls below this calculated value, the compressor will be forced to unload. The value is
measured in the panel pressure units as selected on the
Panel Settings
screen.
3.1.17
Discharge Pressure
Parameter
Units
Minimum
Maximum
Default
High Discharge Pressure Shutdown
barG
-0.01 barG
See Description
14.48 barG
barA
1.00 barA
15.49 barA
PSIG
0.4 inHg
210.0 PSIG
PSIA
14.5 PSIA
224.7 PSIA
kPaG
-1 kPaG
1448 kPaG
kPaA
100 kPaA
1549 kPaA
MPaG
-001 MPaG
1.448 MPaG
MPaA
0.100 MPaA
1.549 MPaA
kg/cm²G
9.8 mmHg
14.76 kg/cm²G
kg/cm²A
1.02 kg/cm²A
15.79 kg/cm²A
High Discharge Pressure Booster
Shutdown
barG
-0.01 barG
17.58 barG
-0.01 barG
barA
1.00 barA
18.59 barA
1.00 barA
PSIG
0.4 inHg
255.0 PSIG
0.4 inHg
PSIA
14.5 PSIA
269.7 PSIA
14.5 PSIA
kPaG
-1 kPaG
1758 kPaG
-1 kPaG
kPaA
100 kPaA
1859 kPaA
100 kPaA
MPaG
-0.001 MPaG
1.758 MPaG
-0.001 MPaG
MPaA
0.100 MPaA
1.859 MPaA
0.100 MPaA
kg/cm²G
9.8 mmHg
17.93 kg/cm²G
9.8 mmHg
Instruction Manual | GEA Omni™
Control panel
Control
Compressor Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
139
Summary of Contents for Omni
Page 1: ...Control panel GEA Omni Instruction Manual E_806550_2 ...
Page 238: ......