3.1.16
Suction Pressure
Parameter
Units
Minimum
Maximum
Default
High Suction Pressure Warning
barG
-0.91 barG
12.78 barG
4.34 barG
barA
0.10 barA
13.79 barA
5.35 barA
PSIG
27.0 inHg
185.3 PSIG
62.9 PSIG
PSIA
1.5 PSIA
200.0 PSIA
77.6 PSIA
kPaG
-91 kPaG
1278 kPaG
434 kPaG
kPaA
10 kPaA
1379 kPaA
535 kPaA
MPaG
-0.091 MPaG
1.278 MPaG
0.434 MPaG
MPaA
0.010 MPaA
1.379 MPaA
0.535 MPaA
kg/cm²G
684.8 mmHg
13.03 kg/cm²G
4.42 kg/cm²G
kg/cm²A
0.10 kg/cm²A
14.06 kg/cm²A
5.45 kg/cm²A
High Suction Pressure Warning
Start Delay
Seconds
0 s
300 s
300 s
Low Suction Pressure Shutdown
barG
-0.91 barG
12.78 barG
-0.03 barG
barA
0.10 barA
13.79 barA
0.98 barA
PSIG
27.0 inHg
185.3 PSIG
1.0 inHg
PSIA
1.5 PSIA
200.0 PSIA
14.2 PSIA
kPaG
-91 kPaG
1278 kPaG
-3 kPaG
kPaA
10 kPaA
1379 kPaA
98 kPaA
MPaG
-0.091 MPaG
1.278 MPaG
-0.003 MPaG
MPaA
0.010 MPaA
1.379 MPaA
0.098 MPaA
kg/cm²G
684.8 mmHg
13.03 kg/cm²G
24.8 mmHg
kg/cm²A
0.10 kg/cm²A
14.06 kg/cm²A
1.00 kg/cm²A
Instruction Manual | GEA Omni™
Control panel
Control
Compressor Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
135