Low Oil Differential Pressure Warning Timer
This parameter is used to select the period of time for which the
Oil Differential Pressure
may exceed the
calculated value for the
Low Oil Differential Pressure Warning
before a
Low Oil Differential Pressure Warn-
ing
is annunciated. The default value of this parameter is dependent on the compressor manufacturer. This
parameter is fixed on Grasso compressors and will not be visible. The value is measured in seconds.
11.
Low Oil Differential Run Delay
This parameter is used to select for what period of time the
Low Oil Differential
parameters will be ignored
after the compressor is started. The default value of this parameter is dependent on the compressor manu-
facturer. The value is measured in seconds.
3.1.13
Oil Filter Pressure
Parameter
Units
Minimum
Maximum
Default
High Oil Filter Differential Shutdown
barG
0.10 barD
20.00 barD
1.38 barD
barA
PSIG
1.5 PSID
290.1 PSID
20.0 PSID
PSIA
kPaG
10 kPaD
2000 kPaD
138 kPaD
kPaA
MPaG
0.010 MPaD
2.000 MPaD
0.138 MPaD
MPaA
kg/cm²G
1.41 kg/cm2D
20.40 kg/cm2D
1.41 kg/cm2D
kg/cm²A
High Oil Filter Differential Warning
Offset
barG
0.10 barD
5.00 barD
1.03 barD
barA
20.00 barD
1.38 barD
PSIG
1.5 PSID
72.5 PSID
14.9 PSID
PSIA
290.1 PSID
20.0 PSID
kPaG
10 kPaD
500 kPaD
103 kPaD
kPaA
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
130
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016