1.
kW Demand Metering Ratio
This parameter is used to display the estimated power demand of the motor while it is running at full
speed. With a 500:5 CT or a 500 A reading with a 20mA input, the value is equal to:
fig.103:
Estimated power demand , calculation formula
P
Estimated power demand
U
Voltage
I
Current
cos φ
Power factor
The value is measured in kW.
2.
kWh Input Pulse Weight
3.
kWh Estimated Usage
This parameter is used to display the current estimate for the total amount of power used by the panel.
The parameter will only be visible ifthe
Power Calculation
option in the configuration is set to something
other than
None
. The value is measured in kWh.
3.1.6
Motor Current
Parameter
Units
Minimum
Maximum
Default
Motor Current Nominal FLA
Amps
1 A
2.000 A
see description
High Motor Current Shutdown Run
Delay
Seconds
0 s
60 s
30 s
High Motor Current Shutdown
Amps
1 A
2.000 A
280 A
High Motor Current Shutdown
Timer
Seconds
1 s
10 s
10 s
High Motor Current Warning Offset
Amps
0 A
300 A
20 A
Illegal Compressor Motor Current
Shutdown
Percent
5 %
20 %
15 %
Low Motor Current Run Delay
Seconds
0 s
30 s
0 s
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
116
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Summary of Contents for Omni
Page 1: ...Control panel GEA Omni Instruction Manual E_806550_2 ...
Page 238: ......