ATTENTION Property damage possible.
The oil level must be in the
visible part of the sight
glass; damage to the com-
pressor is possible if overfil-
led or underfilled!
-50
-45
-40
-35
-30
-25
-15
-20
-5
-10
5
0
t (°C)
C
-20
10
15
t
(°C)
O
-15
?
t
= 10 K
Oh
R744
Fig. 5
Fig. 4
Fig. 4
HGX22e S CO
2
0,5 Ltr.
HGX34e S CO
2
0,7 Ltr.
~
~
~
~
Max. permissible operating
pressure (LP/HP)
1)
: 40/55 bar
Unlimited
application range
Evaporation temperature (°C)
Condensing temperature (°C)
Suction gas superheat (K)
Suction gas temperature (°C)
1)
LP = Low pressure
HP = High pressure
3
|
Areas of application
max.
min.
oil level
ATTENTION Compressor operation is possible within the operating limits
shown in the diagrams. Please note the significance of the shaded
areas. Thresholds should not be selected as design or continuous
operation points.
- Permissible ambient temperature (-20°C) - (+60°C).
- Max. permissible discharge end temperature 160°C.
- Min. oil temperature
≥
30°C.
- Min. pressure gas temperature
≥
50°C.
- Max. permissible switching frequency 8x /h.
- A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved.
For operation with frequency converter:
- Frequency range 25-70 Hz
- The maximum current and power consumption must not be
exceeded. In the case of operation above the mains frequency,
the application limit can therefore be limited.
3.3 Limits of application
The compressors are filled at the factory with the following oil type:
GEA C 85 E (only this oils may be used)
3.1 Refrigerants
•
CO
2
: R744 (Recommendation CO2 quality 4.5 (< 5 ppm H
2
O))
3.2 Oil charge