5.7 Oil sump heater (accessories)
In order to avoid damage to the compressor, the compressor must be equipped with an oil sump heater.
Connexion:
The oil sump heater must be connected via an auxiliary contact (or parallel wired auxiliary
contact) of the compressor contactor to a seperate electric circuit.
Electrical data: 110 - 240 V - 1 - 50/60 Hz, 50 - 120 W, PTC-heater adjusting.
ATTENTION
The oil sump heater must generally be connected and operated!
Relay position INT69 G
B2 12 14 11
Fig. 14
5.6 Function test of the trigger unit INT69 G
Before commissioning, after troubleshooting or making changes to the control power circuit, check
the functionality of the trigger unit. Perform this check using a continuity tester or gauge.
5
|
Electrical connection
Gauge state
Relay position
1.
Deactivated state
11-12
2.
INT69 G switch-on
11-14
3.
Remove PTC connector
11-12
4.
Insert PTC connector
11-12
5.
Reset after mains on
11-14