
14
D
GB
F
E
I
Ru
96260-08.2015-DGbFEIRu
4
|
Compressor assembly
Fig. 19
Fig. 20
Valve spindle seal
Release
Tighten
Pipe connection
Pipe connection
4.8 Operating mode of the lockable service connections
Fig. 21
Opening the shut-off valve:
Spindle: turn to the left (counter-clockwise) as far as it will go.
—> Shut-off valve completely opened / service connection closed.
Fig. 22
Opening the service connection
Spindle: Turn ½ - 1 turn clockwise.
—> Service connection opened / shut-off valve opened.
Connection
blocked
Spindle
Spindle
Connection
open
Compressor
Compressor
Service connec-
tion closed
Service connec-
tion opened
4.7 Operating the shut-off valves
Before opening or closing the shut-off valve, release the valve spindle seal by approx. ¼ of a turn
counter-clockwise.
After activating the shut-off valve, re-tighten the adjustable valve spindle seal clockwise.
After activating the spindle, generally fit the spindle protection cap again and tighten with 14-16 Nm.
This serves as a second sealing feature during operation.