11
GFK-2734
Chapter 11 Technical data and ordering data
11-7
Switching power range (guide value)
60 mW to 1500 W (VA)
Contact resistance
100 m
(when new)
Immunity to short-circuiting
1000 A SCPD (6 A gG backup fuse)
Maximum switching capacity (DIN EN 60947-4-1, DIN EN 60947-5-1)
AC 1
250 V/6 A
AC 15
230 V/3 A
DC 1
24 V/6 A
DC 13
24 V/5 A/0.1 Hz
Maximum interrupting rating for ohmic load (
= 0 ms)
24 V DC
144 W
48 V DC
96 W
110 V DC
66 W
250 V DC
63 W
250 V AC
1500 VA
Maximum interrupting rating for inductive load (
= 40 ms)
24 V DC
35 W
48 V DC
35 W
110 V DC
35 W
250 V DC
35 W
Contact data for the safety relay used [...]
Clock outputs
Number
2
Supply
From U
M
Maximum switching current
15 mA short-circuit and overload protection, approximately
Simultaneity
100%
Derating
No
Status indicators
None
Diagnostic indicators
None
Alarm inputs
Number
2
Supply
From clock outputs UT1 and UT2
Typical input current
5.5 mA
Simultaneity
100%
Derating
No
Status indicators
One green LED per alarm input
(see "Local diagnostic and status indicators" on page 2-10)
Diagnostic indicators
None