11.7
Change/Read Number of Words to Checksum
Use SVCREQ 6 to read or change the number of words in the program to be
checksummed. The function is successful unless some number other than 0 or 1 is entered
as the requested operation.
11.7.1
Parameter Block Formats for SVCREQ 6
The parameter block has a length of 2 words.
To read the word count, the first word of the parameter block must contain a zero:
address
0 (read word count)
a 1
ignored
The function returns the current word count in the second word of the parameter block.
address
0
a 1
current word count
To change the word count, the first word of the parameter block must contain a one:
address
1 (change word count)
a 1
new word count (0 to 32)
The PLC will change the number of words to be checksummed to the new value.
The Service Request Function
GFK-1503E User Manual 203