GE Multilin
T60 Transformer Protection System
2-17
2 PRODUCT DESCRIPTION
2.2 SPECIFICATIONS
2
IRIG-B INPUT
Amplitude modulation:
1 to 10 V pk-pk
DC shift:
TTL
Input impedance:
22 k
Ω
Isolation:
2 kV
REMOTE INPUTS (IEC 61850 GSSE/GOOSE)
Input points:
32, configured from 64 incoming bit pairs
Remote devices:
16
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Remote DPS inputs:
5
DIRECT INPUTS
Input points:
32
Remote devices:
16
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Ring configuration:
Yes, No
Data rate:
64 or 128 kbps
CRC:
32-bit
CRC alarm:
Responding to:
Rate of messages failing the CRC
Monitoring message count: 10 to 10000 in steps of 1
Alarm threshold:
1 to 1000 in steps of 1
Unreturned message alarm:
Responding to:
Rate of unreturned messages in the ring
configuration
Monitoring message count: 10 to 10000 in steps of 1
Alarm threshold:
1 to 1000 in steps of 1
TELEPROTECTION
Input points:
16
Remote devices:
3
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Ring configuration:
No
Data rate:
64 or 128 kbps
CRC:
32-bit
2.2.6 POWER SUPPLY
LOW RANGE
Nominal DC voltage:
24 to 48 V
Minimum DC voltage:
20 V
Maximum DC voltage:
60 V
Voltage loss hold-up:
20 ms duration at nominal
NOTE: Low range is DC only.
HIGH RANGE
Nominal DC voltage:
125 to 250 V
Minimum DC voltage:
88 V
Maximum DC voltage:
300 V
Nominal AC voltage:
100 to 240 V at 50/60 Hz
Minimum AC voltage:
88 V at 25 to 100 Hz
Maximum AC voltage:
265 V at 25 to 100 Hz
Voltage loss hold-up:
200 ms duration at nominal
ALL RANGES
Volt withstand:
2
×
Highest Nominal Voltage for 10 ms
Power consumption:
typical = 15 to 20 W/VA
maximum = 50 W/VA
contact factory for exact order code con-
sumption
INTERNAL FUSE
RATINGS
Low range power supply: 8 A / 250 V
High range power supply: 4 A / 250 V
INTERRUPTING CAPACITY
AC:
100 000 A RMS symmetrical
DC:
10 000 A
2.2.7 OUTPUTS
FORM-A RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous:
6 A
Break (DC inductive, L/R = 40 ms):
Operate time:
< 4 ms
Contact material:
silver alloy
LATCHING RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous:
6 A as per IEEE C37.90
Break at L/R of 40 ms:
0.25 A DC max. (DC resistive as per IEC
61810-1)
Operate time:
< 4 ms
Contact material:
silver alloy
Control:
separate operate and reset inputs
Control mode:
operate-dominant or reset-dominant
FORM-A VOLTAGE MONITOR
Applicable voltage:
approx. 15 to 250 V DC
Trickle current:
approx. 1 to 2.5 mA
VOLTAGE
CURRENT
24 V
1 A
48 V
0.5 A
125 V
0.3 A
250 V
0.2 A
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...