5.2 PRODUCT SETUP
5 SETTINGS
5
The disconnect switch configuration settings are shown below. Changes to these values will not take effect until the UR is
restarted:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
XSWI CONFIGURATION
The
CLEAR XSWI1 OpCnt
setting represents the disconnect switch operating counter. As disconnect switches operate by
opening and closing, the XSWI operating counter status attribute (OpCnt) increments with every operation. Frequent switch
operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XSWI1.
Since GSSE/GOOSE messages are multicast Ethernet by specification, they are not usually be forwarded by net-
work routers. However, GOOSE messages may be forwarded by routers if the router has been configured for VLAN
functionality.
h) WEB SERVER HTTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
WEB SERVER HTTP PROTOCOL
The T60 contains an embedded web server and is capable of transferring web pages to a web browser such as Microsoft
Internet Explorer or Mozilla Firefox. This feature is available only if the T60 has the ethernet option installed. The web
pages are organized as a series of menus that can be accessed starting at the T60 “Main Menu”. Web pages are available
showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, etc. The web pages can be
accessed by connecting the UR and a computer to an ethernet network. The main menu will be displayed in the web
browser on the computer simply by entering the IP address of the T60 into the “Address” box on the web browser.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
XSWI
CONFIGURATION
XSWI1 ST.LOC OPERAND
Off
Range: FlexLogic™ operand
MESSAGE
XSWI2 ST.LOC OPERAND
Off
Range: FlexLogic™ operand
MESSAGE
XSWI3 ST.LOC OPERAND
Off
Range: FlexLogic™ operand
↓
MESSAGE
XSWI24 ST.LOC OPERAND
Off
Range: FlexLogic™ operand
MESSAGE
CLEAR XSWI1 OpCnt:
No
Range: No, Yes
MESSAGE
CLEAR XSWI2 OpCnt:
No
Range: No, Yes
MESSAGE
CLEAR XSWI3 OpCnt:
No
Range: No, Yes
↓
MESSAGE
CLEAR XSWI24 OpCnt:
No
Range: No, Yes
WEB SERVER
HTTP PROTOCOL
HTTP TCP PORT
NUMBER: 80
Range: 1 to 65535 in steps of 1
NOTE
NOTE
Summary of Contents for UR T60
Page 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Page 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...