GE Multilin
L60 Line Phase Comparison System
3-15
3 HARDWARE
3.2 WIRING
3
Figure 3–16: FORM-A AND SOLID STATE CONTACT FUNCTIONS
The operation of voltage and current monitors is reflected with the corresponding FlexLogic™ operands (
CONT OP # VON
,
CONT OP # VOFF
,
CONT OP # ION
, and
CONT OP # IOFF
) which can be used in protection, control and alarm logic. The typical
application of the voltage monitor is breaker trip circuit integrity monitoring; a typical application of the current monitor is
seal-in of the control command.
Refer to the
Digital elements
section of chapter 5 for an example of how form-A and solid-state relay contacts can be
applied for breaker trip circuit integrity monitoring.
Relay contacts must be considered unsafe to touch when the unit is energized! If the relay contacts need to
be used for low voltage accessible applications, it is the customer’s responsibility to ensure proper insula-
tion levels!
USE OF FORM-A AND SOLID-STATE RELAY OUTPUTS IN HIGH IMPEDANCE CIRCUITS
For form-A and solid-state relay output contacts internally equipped with a voltage measuring cIrcuit across the
contact, the circuit has an impedance that can cause a problem when used in conjunction with external high input
impedance monitoring equipment such as modern relay test set trigger circuits. These monitoring circuits may con-
tinue to read the form-A contact as being closed after it has closed and subsequently opened, when measured as
an impedance.
The solution to this problem is to use the voltage measuring trigger input of the relay test set, and connect the form-
A contact through a voltage-dropping resistor to a DC voltage source. If the 48 V DC output of the power supply is
used as a source, a 500
Ω
, 10 W resistor is appropriate. In this configuration, the voltage across either the form-A
contact or the resistor can be used to monitor the state of the output.
Wherever a tilde “~” symbol appears, substitute with the slot position of the module; wherever a number
sign "#" appears, substitute the contact number
When current monitoring is used to seal-in the form-A and solid-state relay contact outputs, the Flex-
Logic™ operand driving the contact output should be given a reset delay of 10 ms to prevent damage of
the output contact (in situations when the element initiating the contact output is bouncing, at values in the
region of the pickup value).
Load
I
~#a
~#b
~#c
If Idc
1mA,
otherwise
³
Cont Op ## Von
Cont Op ## Voff
V
827862A2.CDR
+
+
+
+
+
-
-
-
-
-
a) Voltage with optional
current monitoring
Voltage monitoring only
Load
I
V
Both voltage and current monitoring
If Idc
80mA,
otherwise
³
Cont Op ## Ion
Cont Op ## Ioff
If Idc
1mA,
otherwise
³
Cont Op ## Von
Cont Op ## Voff
Load
I
V
b) Current with optional
voltage monitoring
Current monitoring only
Both voltage and current monitoring
(external jumper a-b is required)
If Idc
80mA,
otherwise
³
Cont Op ## Ion
Cont Op ## Ioff
Load
V
If Idc
80mA,
otherwise
³
Cont Op ## Ion
Cont Op ## Ioff
If Idc
1mA,
otherwise
³
Cont Op ## Von
Cont Op ## Voff
Load
c) No monitoring
~#a
~#b
~#c
~#a
~#b
~#c
~#a
~#b
~#c
~#a
~#b
~#c
I
WARNING
NOTE
NOTE
NOTE
Summary of Contents for UR series
Page 2: ......
Page 4: ......
Page 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Page 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...