5 SETTINGS
5.5 GROUPED ELEMENTS
5
c) GROUND DISTANCE
PATH: SETTINGS
ÖØ
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
ÖØ
DISTANCE
ÖØ
GROUND DISTANCE Z1(Z3)
GROUND DISTANCE Z1
GND DIST Z1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
GND DIST Z1 DIR:
Forward
Range: Forward, Reverse, Non-directional
MESSAGE
GND DIST Z1
SHAPE: Mho
Range: Mho, Quad
MESSAGE
GND DIST Z1
Z0/Z1 MAG: 2.70
Range: 0.00 to 10.00 in steps of 0.01
MESSAGE
GND DIST Z1
Z0/Z1 ANG: 0°
Range: –90 to 90° in steps of 1
MESSAGE
GND DIST Z1
ZOM/Z1 MAG: 0.00
Range: 0.00 to 7.00 in steps of 0.01
MESSAGE
GND DIST Z1
ZOM/Z1 ANG: 0°
Range: –90 to 90° in steps of 1
MESSAGE
GND DIST Z1
REACH: 2.00
Ω
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
GND DIST Z1
RCA: 85°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1 REV
REACH: 2.00
Ω
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
GND DIST Z1 REV
REACH RCA: 85°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1 POL
CURRENT: Zero-seq
Range: Zero-seq, Neg-seq
MESSAGE
GND DIST Z1 NON-
HOMOGEN ANG: 0.0°
Range: –40.0 to 40.0° in steps of 0.1
MESSAGE
GND DIST Z1
COMP LIMIT: 90°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1
DIR RCA: 85°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1
DIR COMP LIMIT: 90°
Range: 30 to 90° in steps of 1
MESSAGE
GND DIST Z1 QUAD
RGT BLD: 10.00
Ω
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
GND DIST Z1 QUAD
RGT BLD RCA: 85°
Range: 60 to 90° in steps of 1
MESSAGE
GND DIST Z1 QUAD
LFT BLD: 10.00
Ω
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
GND DIST Z1 QUAD
LFT BLD RCA: 85°
Range: 60 to 90° in steps of 1
MESSAGE
GND DIST Z1
SUPV: 0.200 pu
Range: 0.050 to 30.000 pu in steps of 0.001
Summary of Contents for UR series
Page 2: ......
Page 4: ......
Page 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Page 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...