GE Multilin
L90 Line Current Differential System
5-333
5 SETTINGS
5.7 CONTROL ELEMENTS
5
Figure 5–172: EXAMPLE RECLOSING SEQUENCE
AR 1P INIT
PREF
AUL
T
F A U L T
R E S E T
1
SHOT
ST
2
SHOT
ND
T PROT
T TRIP BKR
T PROT RESET
T R I P
AR RIP
AR 1-P RIP
AR FORCE 3P TRIP
CLOSE
AR CLOSE BKR1
T CLOSE BKR1
T TRIP BKR
T PROT RESET
3-P/2 DEAD TIME
TRANSFER TIME
T CLOSE BKR2
842703A4.CDR
T PROT
T CLOSE BKR1
RESET TIME
AR RESET TIME
AR SHOT COUNT > 0
BREAKER 1 CLOSED
AR 3P INIT
AR 3P/2 RIP
BREAKER 2 CLOSED
AR CLOSE BKR2
AR TRANSFER TIME
AR INCOMPLETE SEQ. TIME
1-P DEAD TIME
1.25 cycle