GE Multilin
L90 Line Current Differential System
5-321
5 SETTINGS
5.7 CONTROL ELEMENTS
5
5.7.14 AUTORECLOSE
PATH: SETTINGS
CONTROL ELEMENTS
AUTORECLOSE
AUTORECLOSE
AUTORECLOSE
AR FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
AR MODE:
Mode 1 (1 & 3 Pole)
Range: Mode 1(1 & 3 Pole), Mode 2 (1 Pole), Mode 3 (3
Pole-A), Mode 4 (3 Pole-B)
MESSAGE
Mode 1 Activation:
Off
Range: FlexLogic operand
MESSAGE
Mode 2 Activation:
Off
Range: FlexLogic operand
MESSAGE
Mode 3 Activation:
Off
Range: FlexLogic operand
MESSAGE
Mode 4 Activation:
Off
Range: FlexLogic operand
MESSAGE
AR MAX NUMBER OF
SHOTS: 2
Range: 1, 2, 3, 4
MESSAGE
AR INITIATE MODE:
Protection AND CB
Range: Protection AND CB, Protection Only
MESSAGE
AR BLOCK BKR1:
Off
Range: FlexLogic operand
MESSAGE
AR CLOSE TIME BKR 1:
0.10 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR BKR MAN CLOSE:
Off
Range: FlexLogic operand
MESSAGE
AR BLK TIME UPON MAN
CLS:
10.00 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR 1P INIT:
Off
Range: FlexLogic operand
MESSAGE
AR 3P INIT:
Off
Range: FlexLogic operand
MESSAGE
AR 3P TD INIT:
Off
Range: FlexLogic operand
MESSAGE
AR MULTI-P FAULT:
Off
Range: FlexLogic operand
MESSAGE
BKR ONE POLE OPEN:
Off
Range: FlexLogic operand
MESSAGE
BKR 3 POLE OPEN:
Off
Range: FlexLogic operand
MESSAGE
AR 3-P DEAD TIME 1:
0.50 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR 3-P DEAD TIME 2:
1.20 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR 3-P DEAD TIME 3:
2.00 s
Range: 0.00 to 655.35 s in steps of 0.01
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...