5.7 CONTROL ELEMENTS
5 SETTINGS
5
•
CT FAIL 3V0 INPUT PICKUP:
This setting specifies the pickup value for the 3V_0 source.
•
CT FAIL PICKUP DELAY:
This setting specifies the pickup delay of the CT failure element.
Figure 5–154: CT FAILURE DETECTOR SCHEME LOGIC