GE Multilin
L90 Line Current Differential System
5-283
5 SETTINGS
5.7 CONTROL ELEMENTS
5
Figure 5–152: BREAKER RESTRIKE SCHEME LOGIC
e) CONTINUOUS MONITOR
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
CONTINUOUS MONITOR
CONTINUOUS MONITOR
CONT MONITOR
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
CONT MONITOR I-OP:
Off
Range: FlexLogic operand
Any Current Element(s) OP
MESSAGE
CONT MONITOR I-SUPV:
Off
Range: FlexLogic operand
To supervise current logic, use 50DD OP
MESSAGE
CONT MONITOR V-OP:
Off
Range: FlexLogic operand
Any Voltage Element(s) OP
MESSAGE
CONT MONITOR V-SUPV:
Off
Range: FlexLogic operand. To supervise voltage logic,
use VT FUSE FAIL OP
MESSAGE
CONT MONITOR
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
CONT MONITOR
EVENTS: Disabled
Range: Disabled, Enabled
RUN
Current interruption
detection logic
< 0.05 pu
for > ¼ cycle
I
t
mag
ARMED
RESET
SETTING
= Enabled
BREAKER RESTRIKE 1
FUNCTION
SETTING
= Off
BKR RSTR 1 BLK
AND
SETTING
= IA
BREAKER RESTRIKE 1
SOURCE
= IB
= IC
SETTING
= Off
BKR RSTR 1 BKR OPEN
SETTING
= Off
BKR RSTR 1 OPEN CMD
SETTING
= Off
BKR RSTR 1 CLS CMD
AND
OR
SETTING
BREAKER RESTRIKE 1 PICKUP
RUN
Restrike detection logic
0
T
RST
SETTING
BREAKER RESTRIKE 1
RESET DELAY
0
T
RST
0
T
RST
FLEXLOGIC OPERANDS
BKR RESTRIKE 1 OP A
BKR RESTRIKE 1 OP B
BKR RESTRIKE 1 OP C
BKR RESTRIKE 1 OP
FLEXLOGIC OPERAND
OR
834012A1.CDR
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...