5-152
L90 Line Current Differential System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
5.6.3 LINE DIFFERENTIAL ELEMENT
a) MAIN MENU
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
LINE DIFFERENTIAL ELEMENT
b) CURRENT DIFFERENTIAL
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
LINE DIFFERENTIAL...
CURRENT DIFFERENTIAL
LINE DIFFERENTIAL
ELEMENT
CURRENT
DIFFERENTIAL
MESSAGE
STUB BUS
CURRENT
DIFFERENTIAL
CURRENT DIFF
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
CURRENT DIFF SIGNAL
SOURCE 1: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
CURRENT DIFF SIGNAL
SOURCE 2: None
Range: None, SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
CURRENT DIFF SIGNAL
SOURCE 3: None
Range: None, SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
CURRENT DIFF SIGNAL
SOURCE 4: None
Range: None, SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
CURRENT DIFF BLOCK:
Off
Range: FlexLogic operand
MESSAGE
CURRENT DIFF
PICKUP: 0.20 pu
Range: 0.10 to 4.00 pu in steps of 0.01
MESSAGE
CURRENT DIFF
CT TAP 1: 1.00
Range: 0.20 to 5.00 in steps of 0.01
MESSAGE
CURRENT DIFF
CT TAP 2: 1.00
Range: 0.20 to 5.00 in steps of 0.01
MESSAGE
CURRENT DIFF
RESTRAINT 1: 30%
Range: 1 to 50% in steps of 1
MESSAGE
CURRENT DIFF
RESTRAINT 2: 50%
Range: 1 to 70% in steps of 1
MESSAGE
CURRENT DIFF
BREAK PT: 1.0 pu
Range: 0.0 to 20.0 pu in steps of 0.1
MESSAGE
INRUSH INHIBIT MODE:
Disabled
Range: Disabled, Per phase, 2-out-of-3, Average
MESSAGE
INRUSH INHIBIT
LEVEL: 20% fo
Range: 1.0 to 40.0% f
0
in steps of 0.1
MESSAGE
CURRENT DIFF GND
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
CURRENT DIFF GND
PICKUP: 0.10 pu
Range: 0.05 to 1.00 pu in steps of 0.01
MESSAGE
CURRENT DIFF GND
RESTRAINT: 25%
Range: 1 to 50% in steps of 1
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...