5-122
L90 Line Current Differential System
GE Multilin
5.4 SYSTEM SETUP
5 SETTINGS
5
k) PMU RECORDING
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT
PHASOR MEASUREMENT UNIT1
RECORDING PMU1
•
PMU 1 FUNCTION
: This setting enables or disables the recorder for PMU 1. The rate is fixed at the reporting rate set
within the aggregator (i.e., Aggregator 1).
•
PMU 1 NO OF TIMED RECORDS
: This setting specifies the number of timed records that are available for a given log-
ical PMU 1(4). The length of each record is equal to the available memory divided by the content size and number of
records. As the number of records is increased the available storage for each record is reduced. The relay supports a
maximum of 128 records in either timed or forced mode.
•
PMU 1 TRIGGER MODE
: This setting specifies what happens when the recorder uses its entire available memory
storage. Under the “Automatic Overwrite”, the last record is erased to facilitate new recording, when triggered. Under
the “Protected” selection, the recorder stops creating new records when the entire memory is used up by the old un-
cleared records.
•
PMU 1 TIMED TRIGGER POSITION
: This setting specifies the amount of pre-trigger data as a percent of the entire
record. This setting applies only to the timed mode of recording.
l) AGGREGATORS
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
PMU AGGREGATOR 1
When the protocol selection is set via the software or keypad, all aggregators whose protocol is not set to None will
be set to the last protocol saved (i.e., C37.118 or IEC61850-90-5) to any aggregators, as both C37.118 and
IEC61850-90-5 simultaneous streaming of both R-SV values is not possible.
PMU 1
RECORDING
PMU 1 FUNCTION
DISABLE
Range: Enable, Disable
MESSAGE
PMU 1 NO OF TIMED
RECORDS: 10
Range: 2 to 128 in steps of 1
MESSAGE
PMU 1 TRIGGER MODE:
AUTOMATIC OVERWRITE
Range: Automatic Overwrite, Protected
MESSAGE
PMU 1 TIMED TRIGGER
POSITION: 10%
Range: 1 to 50% in steps of 1
PMU AGGREGATOR 1
PMU AGGREGATOR 1
PROTOCOL: NONE
Range: NONE, 37.118, IEC 61850-90-5
Default: NONE
MESSAGE
PMU AGGREGATOR 1:
IDCODE: 1
Range: 1 to 65534 in steps of 1
Default: 1
MESSAGE
PMU AGGREGATOR1:
PORT: 1
Range: 1, 2, 3
Default: 1
MESSAGE
PMU AGGREGATOR 1
INCLUDE PMU1: No
Range: No, Yes
Default: No
MESSAGE
PMU AGGREGATOR 1
INCLUDE PMU2: No
Range: No, Yes
Default: No
MESSAGE
PMU AGGREGATOR 1
INCLUDE PMU3: No
Range: No, Yes
Default: No
MESSAGE
PMU AGGREGATOR 1
INCLUDE PMU4: No
Range: No, Yes
Default: No
MESSAGE
37.118 AGGR 1
CONFIGURATION
See below.
MESSAGE
90-5 AGGR 1
CONFIGURATION
See below.
NOTE
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...