GE Multilin
L90 Line Current Differential System
5-67
5 SETTINGS
5.2 PRODUCT SETUP
5
Refer to the
Control of setting groups
example in the
Control elements
section of this chapter for group activation.
5.2.13 USER-PROGRAMMABLE SELF-TESTS
For user-programmable self-tests for CyberSentry, use the
Setup > Security > Supervisory
menu instead.
PATH: SETTINGS
PRODUCT SETUP
USER-PROGRAMMABLE SELF TESTS
All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets. Most
of the minor alarms can be disabled if desired.
When in the “Disabled” mode, minor alarms will not assert a FlexLogic operand, write to the event recorder, or display tar-
get messages. Moreover, they will not trigger the
ANY MINOR ALARM
or
ANY SELF-TEST
messages. When in the “Enabled”
mode, minor alarms continue to function along with other major and minor alarms. Refer to the
Relay self-tests
section in
chapter 7 for additional information on major and minor self-test alarms.
5.2.14 CONTROL PUSHBUTTONS
PATH: SETTINGS
PRODUCT SETUP
CONTROL PUSHBUTTONS
CONTROL PUSHBUTTON 1(7)
There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced front
panels. These are user-programmable and can be used for various applications such as performing an LED test, switching
setting groups, and invoking and scrolling though user-programmable displays.
Firmware revisions 3.2x and older use these three pushbuttons for manual breaker control. This functionality has been
retained – if the breaker control feature is configured to use the three pushbuttons, they cannot be used as user-program-
mable control pushbuttons.
USER-PROGRAMMABLE
SELF TESTS
REMOTE DEVICE OFF
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
FIRST ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
MESSAGE
SEC. ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
MESSAGE
THIRD ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
MESSAGE
BATTERY FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
SNTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
IRIG-B FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
PTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
SFP MODULE FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
CONTROL
PUSHBUTTON 1
CONTROL PUSHBUTTON 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
CONTROL PUSHBUTTON 1
EVENTS: Disabled
Range: Disabled, Enabled
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...