B-48
L90 Line Current Differential System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
7235
Neutral Directional Overcurrent 1 Forward Pickup
0.006 to 30
pu
0.001
F001
50
7236
Neutral Directional Overcurrent 1 Reverse Limit Angle
40 to 90
degrees
1
F001
90
7237
Neutral Directional Overcurrent 1 Reverse Pickup
0.002 to 30
pu
0.001
F001
50
7238
Neutral Directional Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7239
Neutral Directional Overcurrent 1 Block
0 to 65535
---
1
F300
0
723B
Neutral Directional Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
723C
Neutral Directional Overcurrent 1 Polarizing Voltage
0 to 1
---
1
F231
0 (Calculated V0)
723D
Neutral Directional Overcurrent 1 Op Current
0 to 1
---
1
F196
0 (Calculated 3I0)
723E
Neutral Directional Overcurrent 1 Offset
0 to 250
ohms
0.01
F001
0
723F
Neutral Directional Overcurrent 1 Pos Seq Restraint
0 to 0.5
---
0.001
F001
63
7240
Reserved
0 to 1
---
1
F001
0
7241
...Repeated for Neutral Directional Overcurrent 2
Negative-sequence directional overcurrent (read/write grouped settings) (2 modules)
7260
Negative Sequence Directional Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
7261
Negative Sequence Directional Overcurrent 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7262
Negative Sequence Directional Overcurrent 1 Type
0 to 1
---
1
F179
0 (Neg Sequence)
7263
Neg Sequence Directional Overcurrent 1 Forward ECA
0 to 90
° Lag
1
F002
75
7264
Neg Seq Directional Overcurrent 1 Forward Limit Angle
40 to 90
degrees
1
F001
90
7265
Neg Sequence Directional Overcurrent 1 Forward Pickup
0.015 to 30
pu
0.05
F001
5
7266
Neg Seq Directional Overcurrent 1 Reverse Limit Angle
40 to 90
degrees
1
F001
90
7267
Neg Sequence Directional Overcurrent 1 Reverse Pickup
0.015 to 30
pu
0.05
F001
5
7268
Negative Sequence Directional Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7269
Negative Sequence Directional Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
726B
Negative Sequence Directional Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
726C
Negative Sequence Directional Overcurrent 1 Offset
0 to 250
ohms
0.01
F001
0
726D
Neg Seq Directional Overcurrent 1 Pos Seq Restraint
0 to 0.5
---
0.001
F001
63
726E
Reserved (3 items)
0 to 1
---
1
F001
0
7271
...Repeated for Neg Seq Directional Overcurrent 2
Disconnect Switch (Read/Write setting) (24 modules)
74A0
Disconnect switch 1 function
0 to 1
---
1
F102
0 (Disabled)
74A1
Disconnect switch 1 name
---
---
---
F206
“SW 1"
74A4
Disconnect switch 1 mode
0 to 1
---
1
F157
0 (3-Pole)
74A5
Disconnect switch 1 open
0 to 4294967295
---
1
F300
0
74A7
Disconnect switch 1 block open
0 to 4294967295
---
1
F300
0
74A9
Disconnect switch 1 close
0 to 4294967295
---
1
F300
0
74AB
Disconnect switch 1 block close
0 to 4294967295
---
1
F300
0
74AD
Disconnect switch 1 phase A / three-pole closed
0 to 4294967295
---
1
F300
0
74AF
Disconnect switch 1 phase A / three-pole opened
0 to 4294967295
---
1
F300
0
74B1
Disconnect switch 1 phase B closed
0 to 4294967295
---
1
F300
0
74B3
Disconnect switch 1 phase B opened
0 to 4294967295
---
1
F300
0
74B5
Disconnect switch 1 phase C closed
0 to 4294967295
---
1
F300
0
74B7
Disconnect switch 1 phase C opened
0 to 4294967295
---
1
F300
0
74B9
Disconnect switch 1 operate time
0 to 65.535
s
0.001
F001
70
74BA
Disconnect switch 1 alarm delay
0 to 65.535
s
0.001
F003
0
74BC
Disconnect switch 1 events
0 to 1
---
1
F102
0 (Disabled)
74BD
Reserved (2 items)
---
---
---
---
---
74BF
...Repeated for module number 2
Thermal Overload Protecttion (Read/Write Settings) (2 modules)
7788
Thermal Protection 1 Function
0 to 1
---
1
F102
0 (Disabled)
7789
Thermal Protection 1 Source
0 to 5
---
1
F167
0 (SRC 1)
778A
Thermal Protection 1 Base Current
0.2 to 3
pu
0.01
F001
80
778B
Thermal Protection 1 K Factor
1 to 1.2
---
0.05
F001
110
778C
Thermal Protection 1 Trip Time Constant
0 to 1000
min.
1
F001
45
778D
Thermal Protection 1 Reset Time Constant
0 to 1000
min.
1
F001
45
Table B–9: MODBUS MEMORY MAP (Sheet 40 of 72)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...