B.4 MEMORY MAPPING
B
40BA
DNP energy default deadband
0 to 100000000
---
1
F003
30000
40BC
DNP power factor default deadband
0 to 100000000
--
1
F003
30000
40BE
DNP other default deadband
0 to 100000000
---
1
F003
30000
40C0
DNP IIN time synchronization bit period
1 to 10080
min
1
F001
1440
40C1
DNP message fragment size
30 to 2048
---
1
F001
240
40C2
DNP client address 3
0 to 4294967295
---
1
F003
0
40C4
DNP client address 4
0 to 4294967295
---
1
F003
0
40C6
DNP client address 5
0 to 4294967295
---
1
F003
0
40C8
DNP number of paired binary output control points
0 to 32
---
1
F001
0
40C9
DNP TCP connection timeout
10 to 65535
---
1
F001
120
40CA
DNP communications reserved (22 items)
0 to 1
---
1
F001
0
40E0
TCP port number for the IEC 60870-5-104 protocol
0 to 65535
---
1
F001
2404
40E1
IEC 60870-5-104 protocol function
0 to 1
---
1
F102
0 (Disabled)
40E2
IEC 60870-5-104 protocol common address of ASDU
0 to 65535
---
1
F001
0
40E3
IEC 60870-5-104 protocol cyclic data transmit period
1 to 65535
s
1
F001
60
40E4
IEC 60870-5-104 current default threshold
0 to 100000000
---
1
F003
30000
40E6
IEC 60870-5-104 voltage default threshold
0 to 100000000
---
1
F003
30000
40E8
IEC 60870-5-104 power default threshold
0 to 100000000
---
1
F003
30000
40EA
IEC 60870-5-104 energy default threshold
0 to 100000000
---
1
F003
30000
40EC
IEC 60870-5-104 power default threshold
0 to1
---
0.01
F001
100
40EE
IEC 60870-5-104 other default threshold
0 to 100000000
---
1
F003
30000
40F0
IEC 60870-5-104 client address (5 items)
0 to 4294967295
---
1
F003
0
4104
IEC 60870-5-104 redundancy port
0 to 1
---
1
F126
0 (No)
4105
Port 2 IP Address
0 to 4294967295
---
1
F003
56554706
4107
Port 2 IP Subnet Mask
0 to 4294967295
---
1
F003
4294966272
4109
Port 2 Gateway IP Address
0 to 4294967295
---
1
F003
56554497
410B
PRT2 Ethernet Operation Mode
0 to 1
---
1
F192
1 (Full-Duplex)
410C
PRT2 Redundancy Enabled
0 to 2
---
1
F627
0 (None)
410D
Port 3 IP Address
0 to 4294967295
---
1
F003
56554706
410F
Port 3 IP Subnet Mask
0 to 4294967295
---
1
F003
4294966272
4111
Port 3 Gateway IP Address
0 to 4294967295
---
1
F003
56554497
4113
Port 3 Ethernet Operation Mode
0 to 1
---
1
F192
1 (Full-Duplex)
4114
PRT1 GOOSE Enabled
0 to 1
---
1
F102
1 (Enabled)
4115
PRT2 GOOSE Enabled
0 to 1
---
1
F102
1 (Enabled)
4116
PRT3 GOOSE Enabled
0 to 1
---
1
F102
1 (Enabled)
4119
PRT2 PRP Mcst Addr
---
---
---
F072
0
411C
IEC Communications Reserved (33 items)
0 to 1
---
1
F001
0
413E
High Enet Traffic Function
0 to 1
---
1
F102
0 (Disabled)
413F
High Enet Traffic Events
0 to 1
---
1
F102
0 (Disabled)
4140
DNP object 1 default variation
1 to 2
---
1
F001
2
4141
DNP object 2 default variation
1 to 3
---
1
F001
2
4142
DNP object 20 default variation
0 to 3
---
1
F523
0 (1)
4143
DNP object 21 default variation
0 to 3
---
1
F524
0 (1)
4144
DNP object 22 default variation
0 to 3
---
1
F523
0 (1)
4145
DNP object 23 default variation
0 to 3
---
1
F523
0 (1)
4146
DNP object 30 default variation
1 to 5
---
1
F001
1
4147
DNP object 32 default variation
0 to 5
---
1
F525
0 (1)
Communications Actuals (Read Only)
4160
Modbus Available TCP/IP Connections
0 to 4
---
1
F001
4
4161
DNP Available TCP/IP Connections
0 to 2
---
1
F001
2
4162
IEC Available TCP/IP Connections
0 to 2
---
1
F001
2
4163
MMS Available TCP/IP Connections
0 to 5
---
1
F001
5
4164
PMU Available TCP/IP Connections
0 to 4
---
1
F001
4
Table B–9: MODBUS MEMORY MAP (Sheet 21 of 72)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...