10-28
L90 Line Current Differential System
GE Multilin
10.9 PHASE DISTANCE THROUGH POWER TRANSFORMERS
10 APPLICATION OF SETTINGS
10
d) ZONE 1 SETTING IN APPLICATION (B)
As the transformer is not located between the potential source and the reach point for Z1, the reach impedance must not
include the positive-sequence impedance of the transformer. The CTs are located on the other side of the transformer, thus
transformer ratio must be included:
(EQ 10.22)
e) ZONE 4 SETTING IN APPLICATION (B)
As the transformer is located between the potential source and the reach point for , the reach impedance must include the
positive-sequence impedance of the transformer. The VTs are located on the other side of the transformer, thus transformer
ratio must be included:
10.9.2 EXAMPLE
Given the following for the system shown in the previous section:
Z
X
= 30
85° (intended reach of Zone 1)
Z
H
= 0.06
88° (intended reach of Zone )
n
CT
= 8000:5 = 1600 (located at H)
n
VT
= 315000:120 = 2625 (located at X)
Transformer: 13.8/315 kV, 150 MVA, 10%, delta/wye, 315 kV side lagging 30°
Transformer impedance:
(EQ 10.23)
The Zone 1 settings are:
(EQ 10.24)
PHS DIST Z1 REACH:
"0.80"
PHS DIST Z1 RCA:
"85"
PHS DIST Z1 XMFR VOL CONNECTION:
"None"
PHS DIST Z1 XMFR CUR CONNECTION:
"Dy1"
The settings are:
PHS DIST REACH:
"2.60"
PHS DIST RCA:
"89"
PHS DIST XMFR VOL CONNECTION:
"Yd11"
PHS DIST XMFR CUR CONNECTION:
"None"
Z
1
Z
X
V
H
V
X
-------
n
CT
n
VT
---------
Z
T
at H
10
100
----------
13.8
2
150
-------------------
0.127
90
Z
1
30
13.8
315
-----------
1600
2625
-------------
0.8011
85
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...