GE Multilin
L90 Line Current Differential System
6-9
6 ACTUAL VALUES
6.2 STATUS
6
The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.
6.2.13 FLEX STATES
PATH: ACTUAL VALUES
STATUS
FLEX STATES
There are 256 FlexState
TM
bits available. The second line value indicates the state of the given FlexState bit.
6.2.14 ETHERNET
PATH: ACTUAL VALUES
STATUS
ETHERNET
These values indicate the status of the first, second, and third Ethernet links.
6.2.15 REAL TIME CLOCK SYNCHRONIZING
PATH: ACTUAL VALUES
STATUS
REAL TIME CLOCK SYNCHRONIZING
The RTC Sync Source actual value is the time synchronizing source the relay is using at present. Possible sources are:
Port 1 PTP Clock, Port 2 PTP Clock, Port 3 PTP Clock, IRIG-B, SNTP, and None.
FLEX STATES
PARAM 1:
Off
Off
Range: Off, On
MESSAGE
PARAM 2:
Off
Off
Range: Off, On
MESSAGE
PARAM 256: Off
Off
Range: Off, On
ETHERNET
ETHERNET PRI LINK
STATUS: Fail
Range: Fail, OK
MESSAGE
ETHERNET SEC LINK
STATUS: Fail
Range: Fail, OK
MESSAGE
ETHERNET TRD LINK
STATUS: Fail
Range: Fail, OK
REAL TIME CLOCK
SYNCHRONIZING
RTC Sync Source:
None
Range: See text below
MESSAGE
GrandMaster ID:
0X0000000000000000
Range: Any 8 octet value
MESSAGE
Accuracy:
999,999,999 ns
Range: 0 to 999, 999, 999 ns
MESSAGE
Port 1 PTP State:
NO SIGNAL
Range: Disabled, No Signal, Calibrating, Synch’d (No
Pdelay), Synchronized
MESSAGE
Port 2 PTP State:
NO SIGNAL
Range: Disabled, No Signal, Calibrating, Synch’d (No
Pdelay), Synchronized
MESSAGE
Port 3 PTP State:
NO SIGNAL
Range: Disabled, No Signal, Calibrating, Synch’d (No
Pdelay), Synchronized
MESSAGE
PTP - IRIG-B Delta:
500,000,000 ns
Range: -500,000,000 to +500,000,000 ns
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...