5.7 CONTROL ELEMENTS
5 SETTINGS
5
f) HYBRID PERMISSIVE OVER-REACHING TRANSFER TRIP
PATH: SETTINGS
CONTROL ELEMENTS
PILOT SCHEMES
HYBRID POTT SCHEME
HYBRID POTT SCHEME
HYB POTT SCHEME
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
HYB POTT BLOCK:
Off
Range: FlexLogic operand
MESSAGE
HYB POTT PERMISSIVE
ECHO: Disabled
Range: Disabled, Enabled, Custom
MESSAGE
HYB POTT ECHO COND:
Off
Range: FlexLogic operand
MESSAGE
HYB POTT WEAK
INFEED: Enabled
Range: Disabled, Enabled, Custom
MESSAGE
HYB POTT W/I COND:
Off
Range: FlexLogic operand
MESSAGE
HYB POTT RX PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
TRANS BLOCK PICKUP
DELAY: 0.020 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
TRANS BLOCK RESET
DELAY: 0.090 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
ECHO DURATION:
0.100 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
ECHO LOCKOUT:
0.250 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
HYB POTT SEAL-IN
DELAY: 0.010 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
GND DIR O/C FWD:
Off
Range: FlexLogic operand
MESSAGE
GND DIR O/C REV:
Off
Range: FlexLogic operand
MESSAGE
HYB POTT NO OF COMM
BITS: 1
Range: 1, 2, or 4
MESSAGE
HYB POTT RX1:
Off
Range: FlexLogic operand
MESSAGE
HYB POTT RX2:
Off
Range: FlexLogic operand
MESSAGE
HYB POTT RX3:
Off
Range: FlexLogic operand
MESSAGE
HYB POTT RX4:
Off
Range: FlexLogic operand
MESSAGE
HYB POTT SCHEME
TARGET: Self-Reset
Range: Self-Reset, Latched, Disabled
MESSAGE
HYB POTT EVENT:
Disabled
Range: Disabled, Enabled
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...