5-284
L90 Line Current Differential System
GE Multilin
5.7 CONTROL ELEMENTS
5 SETTINGS
5
The continuous monitor logic is intended to detect the operation of any tripping element that has operated under normal
load conditions; that is, when the disturbance detector has not operated. Because all tripping is supervised by the distur-
bance detector function, no trip will be issued under these conditions. This could occur when an element is incorrectly set
so that it may misoperate under load. The continuous monitor can detect this state and issue an alarm and/or block the trip-
ping of the relay.
Figure 5–153: CONTINUOUS MONITOR SCHEME LOGIC
SETTING
CONT MONITOR
FUNCTION:
Enabled = 1
SETTING
CONSTANT
CONT
MONITOR
TIMER
t
pkp
= 1 sec
t
RST
= 0
CONT MONITOR
I_SUPV:
Off = 0
SETTING
CONT MONITOR
I_OP:
Off = 0
SETTING
CONT MONITOR
V_SUPV:
Off = 0
SETTING
CONT MONITOR
V_OP:
Off = 0
AND
OR
AND
AND
AND
827049A4.CDR
FLEXLOGIC OPERANDS
CONT MONITOR PKP
CONT MONITOR DPO
CONT MONITOR OP
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...