5 SETTINGS
5.6 GROUPED ELEMENTS
5
5.6.7 LOAD ENCROACHMENT
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
LOAD ENCROACHMENT
The load encroachment element responds to the positive-sequence voltage and current and applies a characteristic shown
in the figure below.
Figure 5–91: LOAD ENCROACHMENT CHARACTERISTIC
The element operates if the positive-sequence voltage is above a settable level and asserts its output signal that can be
used to block selected protection elements such as distance or phase overcurrent. The following figure shows an effect of
the load encroachment characteristics used to block the quadrilateral distance element.
LOAD ENCROACHMENT
LOAD ENCROACHMENT
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
LOAD ENCROACHMENT
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
LOAD ENCROACHMENT
MIN VOLT: 0.250 pu
Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
LOAD ENCROACHMENT
REACH: 1.00
Range: 0.02 to 250.00 ohms in steps of 0.01
MESSAGE
LOAD ENCROACHMENT
ANGLE: 30°
Range: 5 to 50° in steps of 1
MESSAGE
LOAD ENCROACHMENT
PKP DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
LOAD ENCROACHMENT
RST DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
LOAD ENCRMNT BLK:
Off
Range: Flexlogic operand
MESSAGE
LOAD ENCROACHMENT
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
LOAD ENCROACHMENT
EVENTS: Disabled
Range: Disabled, Enabled
827846A1.CDR
A
N
G
LE
A
N
G
LE
–REACH
REACH
LOAD ENCROACHMENT
OPERATE
R
X
LOAD ENCROACHMENT
OPERATE
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...