5.4 SYSTEM SETUP
5 SETTINGS
5
5.4.8 PHASOR MEASUREMENT UNIT
a) MAIN MENU
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
The L90 Line Current Differential System is provided with an optional phasor measurement unit feature.
This feature is specified as a software option at the time of ordering. The number of phasor measurement
units available is also dependent on this option. Refer to the
Ordering
section of chapter 2 for additional
details.
UR Synchrophasor Implementation
PHASORS
are used within protection relays. If these phasors are referenced to a common time base they are referred to as
a
SYNCHROPHASOR
. A vastly improved method for tracking power system dynamic phenomena for improved power system
monitoring, protection, operation, and control can be realized if Synchrophasors from different locations within the power
system are networked to a central location.
The L90 offers PMU features over two communication standards, IEC61850-9-5 and C37.118. The complete Synchropha-
sor implementation for Firmware version 7.0 is shown in the figure below.
Figure 5–37: COMPLETE SYNCHROPHASOR IMPLEMENTATION
UR Implementation of IEC61850-90-5
Synchrophasor data as measured and calculated by phasor measurement units (PMUs) is very useful to assess the condi-
tion of the electrical power network. The IEEE C37.118-2005 standard defines synchrophasors and related message for-
mats to transmit synchrophasor data. Synchrophasor streaming via IEEE C37.118 has proven to work but the desire to
PHASOR MEASUREMENT
UNIT
PHASOR MEASUREMENT
UNIT 1
See below.
MESSAGE
AGGREGATOR
UNIT 1
MESSAGE
IEC 90-5 MSVCB
CONFIGURATION
MESSAGE
REPORTING OVER
NETWORK
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...