GE Multilin
L90 Line Current Differential System
5-43
5 SETTINGS
5.2 PRODUCT SETUP
5
The GGIO1 status configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GGIO1 STATUS CONFIGURATION
The
NUMBER OF STATUS POINTS IN GGIO1
setting specifies the number of “Ind” (single point status indications) that are
instantiated in the GGIO1 logical node. Changes to the
NUMBER OF STATUS POINTS IN GGIO1
setting will not take effect until
the L90 is restarted.
The GGIO2 control configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GGIO2 CONTROL CONFIGURATION
GGIO2 CF SPSCO 1(64)
The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0”
(status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the L90
virtual inputs.
The GGIO4 analog configuration points are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GGIO4 ANALOG CONFIGURATION
The
NUMBER OF ANALOG POINTS
setting determines how many analog data points will exist in GGIO4. When this value is
changed, the L90 must be rebooted in order to allow the GGIO4 logical node to be re-instantiated and contain the newly
configured number of analog points.
GGIO1 STATUS
CONFIGURATION
NUMBER OF STATUS
POINTS IN GGIO1: 8
Range: 8 to 128 in steps of 8
MESSAGE
GGIO1 INDICATION
1
Off
Range: FlexLogic operand
MESSAGE
GGIO1 INDICATION
2
Off
Range: FlexLogic operand
MESSAGE
GGIO1 INDICATION
3
Off
Range: FlexLogic operand
MESSAGE
GGIO1 INDICATION 128
Off
Range: FlexLogic operand
GGIO2 CF SPCSO 1
GGIO2 CF SPCSO 1
CTLMODEL: 1
Range: 0, 1, or 2
GGIO4 ANALOG
CONFIGURATION
NUMBER OF ANALOG
POINTS IN GGIO4:
8
Range: 4 to 32 in steps of 4
MESSAGE
GGIO4 ANALOG 1
MEASURED VALUE
MESSAGE
GGIO4 ANALOG 2
MEASURED VALUE
MESSAGE
GGIO4 ANALOG 3
MEASURED VALUE
MESSAGE
GGIO4 ANALOG 32
MEASURED VALUE
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...