GE Multilin
L90 Line Current Differential System
5-9
5 SETTINGS
5.2 PRODUCT SETUP
5
Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry
and the through the faceplate RS232 port. Remote access is defined as any access to settings or commands via any rear
communications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords
enables this functionality.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond-
ing connection password. If the connection is to the back of the L90, the remote password must be used. If the connection
is to the RS232 port of the faceplate, the local password must be used.
The
PASSWORD ACCESS EVENTS
settings allows recording of password access events in the event recorder.
The local setting and command sessions are initiated by the user through the front panel display and are disabled either by
the user or by timeout (via the setting and command level access timeout settings). The remote setting and command ses-
sions are initiated by the user through the EnerVista UR Setup software and are disabled either by the user or by timeout.
The state of the session (local or remote, setting or command) determines the state of the following FlexLogic operands.
•
ACCESS LOC SETG OFF: Asserted when local setting access is disabled.
•
ACCESS LOC SETG ON: Asserted when local setting access is enabled.
•
ACCESS LOC CMND OFF: Asserted when local command access is disabled.
•
ACCESS LOC CMND ON: Asserted when local command access is enabled.
•
ACCESS REM SETG OFF: Asserted when remote setting access is disabled.
•
ACCESS REM SETG ON: Asserted when remote setting access is enabled.
•
ACCESS REM CMND OFF: Asserted when remote command access is disabled.
•
ACCESS REM CMND ON: Asserted when remote command access is enabled.
The appropriate events are also logged in the Event Recorder as well. The FlexLogic operands and events are updated
every five seconds.
A command or setting write operation is required to update the state of all the remote and local security operands
shown above.
b) LOCAL PASSWORDS
PATH: SETTINGS
PRODUCT SETUP
SECURITY
CHANGE LOCAL PASSWORDS
Proper password codes are required to enable each access level. A password consists of 1 to 10 numerical characters.
When a
CHANGE COMMAND PASSWORD
or
CHANGE SETTING PASSWORD
setting is programmed to “Yes” via the front panel
interface, the following message sequence is invoked:
1.
ENTER NEW PASSWORD: ____________.
2.
VERIFY NEW PASSWORD: ____________.
3.
NEW PASSWORD HAS BEEN STORED.
To gain write access to a “Restricted” setting, program the
ACCESS LEVEL
setting in the main security menu to “Setting” and
then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the
password is correctly entered, access will be allowed. Accessibility automatically reverts to the “Restricted” level according
to the access level timeout setting values.
If an entered password is lost (or forgotten), consult the factory with the corresponding
ENCRYPTED PASSWORD
.
CHANGE LOCAL
PASSWORDS
CHANGE COMMAND
PASSWORD: No
Range: No, Yes
MESSAGE
CHANGE SETTING
PASSWORD: No
Range: No, Yes
MESSAGE
ENCRYPTED COMMAND
PASSWORD: ----------
Range: 0 to 9999999999
Note: ---------- indicates no password
MESSAGE
ENCRYPTED SETTING
PASSWORD: ----------
Range: 0 to 9999999999
Note: ---------- indicates no password
NOTE
Summary of Contents for UR Series L90
Page 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...