2-20
C70 Capacitor Bank Protection and Control System
GE Multilin
2.2 SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
2.2.13 APPROVALS
APPROVALS
2.2.14 MAINTENANCE
MOUNTING
Attach mounting brackets using 20 inch-pounds (±2 inch-pounds)
of torque.
CLEANING
Normally, cleaning is not required; but for situations where dust
has accumulated on the faceplate display, a dry cloth can be used.
Units that are stored in a de-energized state should be
powered up once per year, for one hour continuously, to
avoid deterioration of electrolytic capacitors.
COMPLIANCE
APPLICABLE
COUNCIL DIRECTIVE
ACCORDING TO
CE compliance
Low voltage directive
EN60255-5
EMC directive
EN60255-26 / EN50263
EN61000-6-5
North America
---
UL508
---
UL1053
---
C22.2 No. 14
NOTE