6 ACTUAL VALUES
6.3 METERING
6
The metered values for real, reactive, and apparent power, as well as power factor, are displayed in this menu. The "SRC
1" text will be replaced by whatever name was programmed by the user for the associated source (see
SETTINGS
ÖØ
SYS-
TEM SETUP
ÖØ
SIGNAL SOURCES
).
g) FREQUENCY METERING
PATH: ACTUAL VALUES
ÖØ
METERING
Ö
SOURCE SRC 1
ÖØ
FREQUENCY
The metered frequency values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was pro-
grammed by the user for the associated source (see
SETTINGS
ÖØ
SYSTEM SETUP
ÖØ
SIGNAL SOURCES
).
SOURCE FREQUENCY
is measured via software-implemented zero-crossing detection of an AC signal. The signal is either a
Clarke transformation of three-phase voltages or currents, auxiliary voltage, or ground current as per source configuration
(see the
SYSTEM SETUP
ÖØ
POWER SYSTEM
settings). The signal used for frequency estimation is low-pass filtered. The
final frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and
transients.
h) CURRENT HARMONICS AND THD METERING
PATH: ACTUAL VALUES
ÖØ
METERING
Ö
SOURCE SRC 1
ÖØ
CURRENT HARMONICS
The metered current harmonics values are displayed in this menu. The "SRC 1" text will be replaced by whatever name
was programmed by the user for the associated source (see
SETTINGS
ÖØ
SYSTEM SETUP
ÖØ
SIGNAL SOURCES
). Current
harmonics are measured for each source for the total harmonic distortion (THD) and 2nd to 25th harmonics per phase.
MESSAGE
SRC 1 APPARENT PWR
φ
c: 0.000 VA
MESSAGE
SRC 1 POWER FACTOR
3
φ
: 1.000
MESSAGE
SRC 1 POWER FACTOR
φ
a: 1.000
MESSAGE
SRC 1 POWER FACTOR
φ
b: 1.000
MESSAGE
SRC 1 POWER FACTOR
φ
c: 1.000
FREQUENCY
SRC 1
SRC 1 FREQUENCY:
0.00 Hz
CURRENT HARMONICS
SRC 1
SRC 1
THD Ia: 0.0
Ib: 0.0
Ic: 0.0%
MESSAGE
SRC 1
2ND Ia: 0.0
Ib: 0.0
Ic: 0.0%
MESSAGE
SRC 1
3RD Ia: 0.0
Ib: 0.0
Ic: 0.0%
↓
MESSAGE
SRC 1 25TH Ia: 0.0
Ib: 0.0
Ic: 0.0%