6-8
C70 Capacitor Bank Protection and Control System
GE Multilin
6.2 STATUS
6 ACTUAL VALUES
6
6.2.15 IEC 61850 GOOSE INTEGERS
PATH: ACTUAL VALUES
ÖØ
STATUS
ÖØ
IEC 61850 GOOSE UINTEGERS
The C70 Capacitor Bank Protection and Control System is provided with optional IEC 61850 communica-
tions capability. This feature is specified as a software option at the time of ordering. Refer to the
Ordering
section of chapter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E
is ordered.
The IEC 61850 GGIO5 integer input data points are displayed in this menu. The GGIO5 integer data values are received
via IEC 61850 GOOSE messages sent from other devices.
6.2.16 ETHERNET SWITCH
PATH: ACTUAL VALUES
Ö
STATUS
ÖØ
ETHERNET SWITCH
These actual values appear only if the C70 is ordered with an Ethernet switch module (type 2S or 2T). The status informa-
tion for the Ethernet switch is shown in this menu.
•
SWITCH 1 PORT STATUS
to
SWITCH 6 PORT STATUS
: These values represents the receiver status of each port on
the Ethernet switch. If the value is “OK”, then data is being received from the remote terminal; If the value is “FAIL”,
then data is not being received from the remote terminal or the port is not connected.
•
SWITCH MAC ADDRESS
: This value displays the MAC address assigned to the Ethernet switch module.
IEC 61850
GOOSE UINTEGERS
UINT INPUT
1
0
MESSAGE
UINT INPUT
2
0
↓
MESSAGE
UINT INPUT 16
0
ETHERNET SWITCH
SWITCH 1 PORT
STATUS: OK
Range: FAIL, OK
MESSAGE
SWITCH 2 PORT
STATUS: OK
Range: FAIL, OK
↓
MESSAGE
SWITCH 6 PORT
STATUS: OK
Range: FAIL, OK
MESSAGE
SWITCH MAC ADDRESS:
00A0F40138FA
Range: standard MAC address format
Summary of Contents for UR Series C70
Page 2: ......
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...