5-140
C70 Capacitor Bank Protection and Control System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
5.6.6 GROUND CURRENT
a) MAIN MENU
PATH: SETTINGS
ÖØ
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
ÖØ
GROUND CURRENT
The C70 contains protection elements for ground time overcurrent (ANSI device 51G) and ground instantaneous overcur-
rent (ANSI device 50G). A maximum of six ground time overcurrent and eight ground instantaneous overcurrent elements
are available, dependent on the CT/VT modules ordered with the relay. See the following table for details.
GROUND CURRENT
GROUND TOC1
MESSAGE
GROUND TOC2
↓
MESSAGE
GROUND TOC6
MESSAGE
GROUND IOC1
MESSAGE
GROUND IOC2
↓
MESSAGE
GROUND IOC12
CT/VT MODULES
GROUND CURRENT ELEMENTS
SLOT F
SLOT M
TIME
OVERCURRENT
INSTANTANEOUS
OVERCURRENT
8F/8G
8F/8G
4
4
8H/8J
6
6
8H/8J
8F/8G
6
6
8H/8J
6
8