5-70
C70 Capacitor Bank Protection and Control System
GE Multilin
5.4 SYSTEM SETUP
5 SETTINGS
5
5.4.4 BREAKERS
PATH: SETTINGS
ÖØ
SYSTEM SETUP
ÖØ
BREAKERS
Ö
BREAKER 1
BREAKER 1
BREAKER 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
BREAKER1 PUSH BUTTON
CONTROL: Disabled
Range: Disabled, Enabled
MESSAGE
BREAKER 1 NAME:
Bkr 1
Range: up to 6 alphanumeric characters
MESSAGE
BREAKER 1 MODE:
3-Pole
Range: 3-Pole, 1-Pole
MESSAGE
BREAKER 1 OPEN:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 BLK OPEN:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 CLOSE:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 BLK CLOSE:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
A/3P CLSD:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
A/3P OPND:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
B CLOSED:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
B OPENED:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
C CLOSED:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
C OPENED:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 Toperate:
0.070 s
Range: 0.000 to 2.000 s in steps of 0.001
MESSAGE
BREAKER 1 EXT ALARM:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 ALARM
DELAY: 0.000
s
Range: 0.000 to 1 000 000.000 s in steps of 0.001
MESSAGE
MANUAL CLOSE RECAL1
TIME: 0.000
s
Range: 0.000 to 1 000 000.000 s in steps of 0.001
MESSAGE
BREAKER 1 OUT OF SV:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 EVENTS:
Disabled
Range: Disabled, Enabled