GE Multilin
T60 Transformer Protection System
2-1
2 PRODUCT DESCRIPTION
2.1 INTRODUCTION
2
2 PRODUCT DESCRIPTION 2.1INTRODUCTION
2.1.1 OVERVIEW
The T60 Transformer Protection System is a microprocessor-based relay for protection of small, medium, and large three-
phase power transformers. The relay can be configured with a maximum of six three-phase current inputs and six ground
current inputs, and can satisfy applications with transformer windings connected between two breakers, such as in a ring
bus or in breaker-and-a-half configurations. The T60 performs magnitude and phase shift compensation internally, eliminat-
ing requirements for external CT connections and auxiliary CTs.
The percent differential element is the main protection device in the T60. Instantaneous differential protection, volts-per-
hertz, restricted ground fault, and many current, voltage, and frequency-based protection elements are also incorporated.
The T60 includes sixteen fully programmable universal comparators, or FlexElements™, that provide additional flexibility
by allowing the user to customize their own protection functions that respond to any signals measured or calculated by the
relay.
The metering functions of the T60 include true RMS and phasors for currents and voltages, current harmonics and THD,
symmetrical components, frequency, power, power factor, and energy.
Diagnostic features include an event recorder capable of storing 1024 time-tagged events, oscillography capable of storing
up to 64 records with programmable trigger, content and sampling rate, and data logger acquisition of up to 16 channels,
with programmable content and sampling rate. The internal clock used for time-tagging can be synchronized with an IRIG-
B signal, using the Simple Network Time Protocol (SNTP) over the Ethernet port, or using the Precision Time Protocol
(PTP). This precise time stamping allows the sequence of events to be determined throughout the system. Events can also
be programmed (via FlexLogic™ equations) to trigger oscillography data capture which may be set to record the measured
parameters before and after the event for viewing on a personal computer (PC). These tools significantly reduce trouble-
shooting time and simplify report generation in the event of a system fault.
Several options are available for communication. A faceplate RS232 port can be used to connect to a computer for the pro-
gramming of settings and the monitoring of actual values. The RS232 port has a fixed baud rate of 19.2 kbps. The rear
RS485 port allows independent access by operating and engineering staff. It can be connected to system computers with
baud rates up to 115.2 kbps. All serial ports use the Modbus RTU protocol. The IEC 60870-5-103 protocol is supported on
the RS485 interface. IEC 60870-5-103, DNP, and Modbus cannot be enabled simultaneously on this interface. Also only
one of the DNP, IEC 60870-5-103, and IEC 60870-5-104 protocols can be enabled at any time on the relay. When the IEC
60870-5-103 protocol is chosen, the RS485 port has a fixed even parity and the baud rate can be either 9.6 kbps or 19.2
kbps. The 100Base-FX or 100Base-T Ethernet interface provides fast, reliable communications in noisy environments. The
Ethernet port supports IEC 61850, IEC 61850-90-5, Modbus/TCP, and TFTP protocols, PTP (according to IEEE Std. 1588-
2008 or IEC 61588), and allows access to the relay via any standard web browser (T60 web pages). The IEC 60870-5-104
protocol is supported on the Ethernet port. The Ethernet port also supports the Parallel Redundancy Protocol (PRP) of IEC
62439-3 (clause 4, 2012) when purchased as an option.
Settings and actual values can be accessed from the front panel or EnerVista software.
The T60 IEDs use flash memory technology that allows field upgrading as new features are added.
The following
Single line diagram
illustrates the relay functionality using ANSI (American National Standards Institute)
device numbers.
Table 2–1: ANSI DEVICE NUMBERS AND FUNCTIONS
DEVICE
NUMBER
FUNCTION
DEVICE
NUMBER
FUNCTION
21G
Ground distance
51P
Phase time overcurrent
21P
Phase distance
59N
Neutral overvoltage
24
Volts per hertz
59P
Phase overvoltage
25
Synchrocheck
59X
Auxiliary overvoltage
27P
Phase undervoltage
67N
Neutral directional overcurrent
27X
Auxiliary undervoltage
67P
Phase directional overcurrent
49
Thermal overload protection
68
Power swing blocking
50/87
Instantaneous differential overcurrent
78
Out-of-step tripping
50BF
Breaker failure
81O
Overfrequency
50G
Ground instantaneous overcurrent
81R
Rate of change of frequency
50N
Neutral instantaneous overcurrent
81U
Underfrequency
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...